Rev. 1.03 

3.3.1 Block power supply 

+

B

- B

~

   

  ~

B

at

te

ry

 fu

se

Battery fuse

Transformer

GND

Battery

N

L

CASE

TRANSFORMER

+

-

+

-

12V  7Ah

12V  7Ah

DOOR

 

 
The block power supply is composed of: 

1)  Toroidal transformer 230Vac / 33Vac. 
2)  Clips for the connection to the 230Vac: 

a.  Neutral. 
b.  Line. 
c.  GND. 
d.  GND of the case. 
e.  Protection fuse from the 230Vac. 

3)  Two batteries pad of 12V 7Ah. 
4)  Clips for the motherboard power supply: 

a.  (-B, +B) battery pad. 
b.  GND. 
c.  (~ ~) transformer. 
d.  Protection fuse from the battery connection. 

 

WARNING

:  after  the  cable  connection  of  the  power  supply  to  the  GND-N-L  clips  of  AC-DC 

Adaptor,  it  is  important  to  immobilize  the  three  electrical  cables  with  a  plastic  strip.  It  is 
necessary to prevent that electrical cables are free to move. 
 

WARNING

:  the  power  supply  cable  must  have  the  ground  electrical  cable  (GND)  more  long 

respect the line (L) and neuter (N) cables. 

Содержание CFN

Страница 1: ...ONVENTIONAL CONTROL PANEL INSTALLER MANUAL FDP International Group S r l Via Pierobon 20 bis 35010 LIMENA PD ITALY Tel 39 049 767249 fax 39 049 767898 E mail info fdpinternational com www fdpinternati...

Страница 2: ...2 3 5 2 Led of the zone 12 3 5 3 Button descriptions 12 3 6 MAINTENANCE 13 3 6 1 Leds buzzer test 13 3 6 2 Daily control 13 3 6 3 Weekly control 13 3 6 4 Four monthly control 13 3 6 5 Yearly control 1...

Страница 3: ...0 2 LEVEL 2 29 10 3 LEVEL 3 29 PART 11 POINTS DESCRIPTION AND UTILIZATION 30 11 1 DETECTOR 30 11 1 1 Smoke detector 30 11 1 2 Heat detector 30 11 1 3 Multicriterion detector 30 11 1 4 Electrical schem...

Страница 4: ...causes can be the line is too long loose clips false contacts cable of insufficient section partly cut off or damaged cable The cables must usually present a resistor between 10 and 15 Besides the res...

Страница 5: ...tectors GMR GGR GCR Relay output modules All devices with a relay output The detectors must be plain with a low power supply of 50 A when the detector is in normally functioning If it goes to alarm mo...

Страница 6: ...cessive heat and or heating devices can compromise the working and the product integrity Ensure a proper ventilation for the product Humidity or presence of condensation drops can damage the product I...

Страница 7: ...in this manual Insert the 230Vac net line in the case keeping far away the same one from the printed circuits and the rest of wiring Supply to the control panel through a suitable magneto thermic pow...

Страница 8: ...pointed out B B Battery fuse AUX 24V FUSE C NC NO Relay 1 24V aux Out 1 Out 2 C NC NO Relay 2 Line 1 Line 2 3 Line 4 Line 5 Line 6 Line 1 2 3 4 5 6 Open collector Battery fuse Transformer GND Battery...

Страница 9: ...230Vac 3 Two batteries pad of 12V 7Ah 4 Clips for the motherboard power supply a B B battery pad b GND c transformer d Protection fuse from the battery connection WARNING after the cable connection o...

Страница 10: ...rd is composed of 1 One fuse for the 24Vdc aux output protection 2 Two relay outputs N NC NO a Relay 1 for the alarm signalling b Relay 2 normally on for the fault signalling 3 Two supervised siren ou...

Страница 11: ...to the control panel must be fireproof The cable of earth the net ground must be connected to the earth clip of net input 3 4 INSERTION AND REMOVING POINTS To modify insert remove points of a zone it...

Страница 12: ...t of service SIREN Yellow Normally off Slow flashing it indicates the fault status of the siren output open circuit or short circuit Fast flashing it indicates that a siren output is active Fixed ligh...

Страница 13: ...This function lights up all leds and it actives the internal buzzer and fault relay for a time of 5s 3 6 2 Daily control The user will check that The control panel works properly Otherwise the faults...

Страница 14: ...problems as soon as possible 3 6 5 Yearly control The maintenance staff must have the duty to perform the following controls Carry out the control procedures advised daily monthly and four monthly Tes...

Страница 15: ...TTING At first time the control panel has the following setting 1 all zones are in service no out of service 2 all zones are in alarm mode single consent and the Automatic activation property of the O...

Страница 16: ...signals and commands of the control panel are available In this level it is possible to enabled or disabled the zones to activate the outputs to test the leds and the internal buzzer to restore alarms...

Страница 17: ...t the password of level 3 default 333 The led LEVEL is on and it flashes slow To abort the procedure push LEVEL button Procedure to modify the password of level 3 Push LEVEL button the led flashes fas...

Страница 18: ...he alarmed zone is activated output Relay1 active In case of silence mode the leds ALARM and SILENCE remain always on 6 2 PRE ALARM In case a pre alarm mode is engaged just with one detector in alarm...

Страница 19: ...given the POWER FAULT led begins to flash with a slow flash intermittence and the control panel goes to fault status If the fault is restored the control panel is restored too Battery fault If the bat...

Страница 20: ...RESET The control panel reset permits to restore the normal status of the control panel The reset command does 1 restoration of the siren and relay outputs 2 silent mode of the internal buzzer 3 resto...

Страница 21: ...s s End of delay I detector in alarm Buzzer activation II detector of zone in alarm Activation delay Out1 Output activation Out1 no Manual delay reset Output activation Relay1 yes Activation delay Out...

Страница 22: ...as there is at least a zone in out of service NOTE a zone in out of service stands to have a 24Vdc as normal zone If the user wants to do maintenance at a zone it is necessary to put it to out of ser...

Страница 23: ...which the user wants to set pre alarm it is necessary to use the specific resistor see chapter PART 9 Procedure Access at level 3 Push OUT OF SERVICE button The led OUT OF SERVICE flashes with quick i...

Страница 24: ...Page 24 of 35 Rev 1 03 To interrupt the procedure and return to level 1 without having applied any changes press the LEVEL button...

Страница 25: ...tput 1 o To push zone 2 button for output 2 To finish this test procedure to push LEVEL button 8 2 SIREN OUTPUT SILENT If the control panel is in alarm status and the user wants to silence all siren o...

Страница 26: ...into alarm or if an alarm button has been pressed or a device where it is been installed a an alarm resistor If the user wants enable the delay at device with output relay it is necessary to use a pr...

Страница 27: ...cted from a fuse but it is not supervised The control panel does not control the fuse status 24V aux fuse F 315mA L 250V Battery charger 27 6Vdc at 20 C Battery Lead sealed at Pb 24V 7 2Ah Battery fus...

Страница 28: ...Relay output 2 relay outputs C NO NC Relay 1 alarm Relay 2 fault the relay is normally excited Max current Max 1A 30Vdc 0 5A 125Vac OPEN COLLECTOR OUTPUT available only request Open Collector outputs...

Страница 29: ...1 LEVEL 1 Silent mode of 1st level 6 5 10 2 LEVEL 2 Silent mode of 2nd level 5 1 3 Alarm fault reset 0 Leds buzzer test 3 6 1 Out of service of zone 7 1 Siren outputs activation 8 1 10 3 LEVEL 3 Defa...

Страница 30: ...ate itself when the heat exceeds a previously fixed level It is available a heat detector with rate of rise function this detector has been designed to activate itself the speed with which this increm...

Страница 31: ...his button has C NO clips at which to install the alarm resistor see the value at chapter PART 9 NO NC C If the button has inside a resistor the user must control if this resistor has a compatible val...

Страница 32: ...Page 32 of 35 Rev 1 03 11 2 3 Rearmable button with key This type of button has a key for the rearmament in the case if it is pressed The electrical scheme to see chapter of the Glass break button...

Страница 33: ...12 1 SIREN AND ELECTROMAGNET CONNECTION TO THE CONTROL PANEL 24Vcc fuse C NC NO Relay 1 24V aux Out 1 Out 2 C NC NO Relay 2 In 1 In 2 In 3 In 4 In 5 In 6 1 2 3 4 5 6 Open collector 24V aux fuse Relay...

Страница 34: ...24V aux Output 2 Output 1 Zones Open collector ACOUSTIC OPTIC PANEL SIREN 12 3OPEN COLLECTOR CONNECTION AUX 24V FUSE C NC NO Relay 1 24V aux Out 1 Out 2 C NC NO Relay 2 Line 1 Line 2 Line 3 Line 4 Lin...

Страница 35: ...the siren line The end of line resistor missing To check if there is the end of line resistor at the end of siren line SIREN FAULT Siren line loss of balance To check the equivalent resistor of the s...

Отзывы: