5.1 ACCESS LEVELS
5.1.1 Levels for final user and installer
The control panel is has been planned following the EN54-2 norms. This rule gives at least
three different access level.
The access levels are divided as described below.
The control panel is normality status at level 1. To access to superior levels, it is necessary to
insert the appropriated codes.
N.B.: the code of level 3 must be used only by the qualified technician to the
programming of the control panel.
5.1.2 Level 1
Level for the final user. It permits to check the control panel status and to do the silence mode
of the internal buzzer.
5.1.3 Level 2
Access allowed to the system management. All signals and commands of the control panel are
available. In this level it is possible to enabled or disabled the zones, to activate the outputs, to
test the leds and the internal buzzer, to restore alarms or faults and to silence outputs.
Procedure:
•
Push <
LEVEL
> button (the led flashes fast).
•
Insert the password of level 2 (default
222
).
The led <
LEVEL
> is on at fixed light.
To abort the procedure, push <
LEVEL
> button.
Procedure to modify the password of level 2:
•
Push <
LEVEL
> button (the led flashes fast).
•
Insert the password of level 2.
•
Push <
LEVEL
> button within 2 seconds (the leds <
TEST
>, <
OUT OF SERVICE
> and
<
SIREN
> flash fast).
•
Insert the new password of level 2.
•
Reinsert the new password of level 2 (a double beep gives the password change; a long
beep gives a change error).
It is not possible to have the password of level 3 equal to level 2.
To abort the procedure, push <
LEVEL
> button.