VAIE 2000 | Voice Alarm Integrated Systems

System Manual | 2013

UK

VAC 2006 • VAR 2006

8.4.1.4  AMPLIFIER FAuLtS

 

Power amplifier diagnostics and Gnd fault

From the FAULTS panel (point 8.4.1), press numerical key 

3

 and access the 

panel for viewing the power amplifier diagnostics and ground faults of the 

loudspeaker lines. 

The diagnostic state of each item monitored is reported, as shown in the 

following table (Table D).

Press ESC to return to the panel FAULTS.

Label

Part being diagnosed

display

Cause

Action required

All

All

Ok

No failure

-

N.T.

NOT TEST. Diagnostics 

disabled during configuration 

(See 

Set> BACKGROUND 

TEST 

menu)

-

Res.

Failure cleared due to 

previous Fault signal

Access the 

report> FAULTS 

panel from the 

OPERATOR menu and carry out a MANUAL 

RESET of the FAILURE signal.

Amplifier n

Amplifiers of the DPU 

range connected to the 

controller or MPA 5240/48 

amplifiers connected to 

the router

Amp ok

-

Input 20kHz 

Check that the connection 

between the controller and the 

amplifier is sound.

Check that the connections between the 

controller, the amplifier and the router have 

been made correctly.

If the failure persists, contact the Service 

Centre.

Out 20kHz 

Make sure that there is an 

output signal on the line.

Make sure that the amplifier has been 

connected to the network and switched on.

If the failure persists, contact the Service 

Centre.

Gnd Fault 

Check the insulation between 

the loudspeaker lines and 

earth.

Check the connections of the loudspeaker 

lines

. If the failure persists, contact the 

Service Centre.

Tab. 8.4.1.4

Содержание VAIE 2000

Страница 1: ...006 Router MANUALE DI ISTRUZIONI OPERATING MANUAL VAC 2006 Controller __ F BT Aud10 Cont ract or EN 54 16 0068 CPR 001 2014 VAR 2006 VOICE ALARM ROUTER _ F T 1 2 3 4 5 6 COM SYS e e GND ALARM MSG e f...

Страница 2: ...ex buildings effective and inexpensive enabling the use of both centralised and or local equipment Each VAC 2006 controller has provisions for managing 6 control lines to which the following units can...

Страница 3: ...BT 1112 upto7 i B UNEA up to 16 1 dg UNEB UNEA UNEB n 7l 1 _ 1 B UNEA CONTROLLER UNEB UNEA u Z 1 8UNEB VAR2006 ROUTER N 1 6 J VAR2006 ROUTER N 6 ROUTER AND MPA 5000 AMPLIFIERS TO MANAGE ZONE 30 36 MPA...

Страница 4: ...put for a microphone or outside source Terminal block for connecting a precedence contact R6 Input for external microphone R7 Input for connecting an external source of music R8 7 monitored digital in...

Страница 5: ...2250 integrated evacuation systems 4 redundant lines for connections among the various different controllers max 6 2 redundant lines for emergency microphone bases of the FMD range max 7 with 7 priori...

Страница 6: ...Y NOTES Any activities inside the equipment such as maintenance operations and so on must be carried out solely by specialised personnel When the cover is removed parts become accessible that entail a...

Страница 7: ...i ltj _ i o o __F3TVAC2008 CE l________i 1 rn rn rn i i ii l rc0 i M _N Y _Y llllAIIELM1 1 BATTERY 1 VAC 2006 CONTROLLER n O VAR 2006 ROUTER 0 m _CE r r 0 1 f l fi o 0 r i T i i i T i i i T 1 IA n r...

Страница 8: ...ng THE output lines Use the SLAVE LINK OUTPUTS sockets R9 to connect the following to the controller B1 VAR 2006 router B2 VAIE 2250 compact emergency system B3 Amplifiers of the DPU range B1 VAR 2006...

Страница 9: ...e REMOTE LINK socket on the VAIE 2250 compact system B3 Amplifiers of the DPU range Use a Cat 5e SF UTP cable to connect one of the SLAVE LINK OUTPUTS sockets R9 to the IN OUT socket on the amplifier...

Страница 10: ...level of the microphone connected to the IN 1 input To receive select the INPUT 1 BGM source from the MUSIC menu Set the following via the INPUT 1 panel MODE OFF PH OFF The Chime Priority and Zone lis...

Страница 11: ...on do not connect any other equipment to the LInE terminals of the In 2 input C Digital microphone stations connected in cascade formation to the PAGING UNIT input The announcement will be addressed t...

Страница 12: ...ble on the terminals provided R12 E RJ45 input contacts control inputs There are 7 contacts on the CONTROL INPUTS R8 socket An example of a connection is shown in the figure N B In the example contact...

Страница 13: ...ating condition signals that the Alarm signals for at least one output zone have been set to a Disablement condition The system can in any case carry on the functions pertaining to the Quiescent condi...

Страница 14: ...in the following tables The active sources in the Voice Alarm condition always have priority over those active in Quiescent condition regardless of the priority level set Priority System condition Op...

Страница 15: ...keys it is useful for navigating through the menus for adjusting working parameters and for managing advanced functions It will also display all the information required concerning Fault Disablement...

Страница 16: ...ent levels and the group of paging zones The XLR F socket enables a balanced signal of up to 100 mV to be connected by means of shielded balanced microphone cable For details concerning the settings o...

Страница 17: ...g broadcast Flashing Warning message being sent out Steady ON Evacuation or live message being sent out The yellow LINE A B LEDs indicate the following Flashing Zone failure impedance measured on the...

Страница 18: ...he CONTROL socket It is possible to enable diagnostics for the connecting line by installing two 10 kOhm balancing resistors in the proximity of the contact for activating the remote peripheral unit T...

Страница 19: ...inguishes automatically and the wording RES is shown on the FAULTS display to show that a failure has been detected and subsequently remedied RESUMED The LED signalling that the fault has been cleared...

Страница 20: ...e box to assign a name to the project and identify or create a destination folder The status bar at the bottom of the window will show that the operation has been completed successfully Once this has...

Страница 21: ...nused condition VAR 2006 router If you select this item the Line 1 configuration window will open in which you can select the features of the zones and the input and output contacts of the router You...

Страница 22: ...a maximum of two standby units The first of these is global that is to say it can replace the amplifiers of any other line of the controller The second standby unit can be either global if there are...

Страница 23: ...to make changes manually to the default configuration prompted in the Unit key list box Press End to save the configuration or press Canc to cancel it and return to the main window o Emergency unit co...

Страница 24: ...g on the number which will turn green After setting the zones you require click on Save to save the configuration To create the next configuration file select the name in the drop down menu as before...

Страница 25: ...anagement of the pre recorded voice messages and of the warning signal if any Click on Path Add file and load the required wav file N B The files to be used must necessarily be recorded in and or conv...

Страница 26: ...m the PC then plug it into its slot in the rear panel of CONTROLLER 0 Put the cover back into place and fix it with the screws removed earlier Repeat these operations for all the other controllers in...

Страница 27: ...manage the system in emergency failure and disablement conditions A password for accessing this level can be added ConFIGuRAtIon Menu Third access level for trained personnel authorised to use the adv...

Страница 28: ...question it is it is necessary to enter a password and then press Ok again As an alternative press ESC to return to the MUSIC menu From the OPERATOR menu use the knob at the side of the display unit...

Страница 29: ...y to enter another password and then press Ok again As an alternative press ESC to return to the MUSIC menu The Functional Specifications of the panels for managing the SERVICE menu are the responsibi...

Страница 30: ...e procedure is complete see the instructions of the following sections For normal use of background music and voice announcements users can use just MUSIC and AUDIO SETTING menu For the management of...

Страница 31: ...y setting 24 VDC P S ON as illustrated under BACKGROUND TEST point 8 5 2 3 page 104 o Path HOME CONFIGURATION set BACKGROUND TEST 4 Power supplies Emergency messages The emergency messages are stored...

Страница 32: ...ection of a BGM Source for the music channel Press oK to select the required source of music from among the following AUX Microphone source connected to the LINE AUX IN input R7 REMOTE Source selected...

Страница 33: ...ponding to the source then turn the knob to adjust the volume range 80 to 0 dB 8 3 2 set CHIME Management of the warning signal chime Panel for setting the chime that is produced on activating a voice...

Страница 34: ...ed mode from among the following options Z 1 Z 216 To select the specific zone in which you wish to broadcast the calls music All To broadcast the calls music to all the zones in the system C 1 Z 64 T...

Страница 35: ...he PA announcement function The source connected continues to be available for selection as a BGM Source 2 Zone call Setting the operating mode of the input for using the voice channel as a PA source...

Страница 36: ...m the report IMPEDANCE option For viewing in real time the line impedance values detected by the system indicating the percentage of deviation from the value stored at the time of initialising the sys...

Страница 37: ...RES RESUMED in the label of the part that had FAILED The RESOLVED signal will be stored until a MANUAL RESET of the failure signal is carried out from the FAULTS panel via the OPERATOR menu Tab 8 4 1...

Страница 38: ...e panel FAULTS Tab 8 4 1 2 Label Part being diagnosed Signalling Cause Action required ALL OK No failure Line 1 Speaker units Zone 1 Short A Short circuit on the line connected to output A Eliminate t...

Страница 39: ...he SD card has been correctly plugged into its slot on the rear panel of the controller 3 Emerg Unit Emergency microphone stations Fault Failure of at least one emergency microphone station Make sure...

Страница 40: ...of the FAILURE signal Amplifier n Amplifiers of the DPU range connected to the controller or MPA 5240 48 amplifiers connected to the router Amp ok Input 20kHz Check that the connection between the co...

Страница 41: ...e If the failure persists contact the Service Centre Contr 24VDC Secondary power supply of the controller 24Vdc Secondary power supply of the controller not detected Check the 24 VDC power supply the...

Страница 42: ...unication failure Contact the Service Centre Tab 8 4 1 7 Label Part being diagnosed Display Cause Action required No input fault found Input contacts 1 to 8 Empty list No failure or monitoring not ena...

Страница 43: ...efined by the firmware controller exe 8 4 5 INDICATORS TEST Check of the functionality of the visual and audio signal elements Panel for checking speaker functionality BEEP display and operating emerg...

Страница 44: ...the firmware installed in the system InSPECtIon For going directly to the INSPECTION menu ConFIGuRAtIon For going directly to the CONFIGURATION menu 8 5 5 Exit Logout option To exit from the service...

Страница 45: ...8 5 2 5 or press ESC to return to the OPERATOR menu 8 5 2 1 VOICE ALARMS Setting the Test for Emergency Sources Panel for enabling and disabling the monitoring tests Press the corresponding numerical...

Страница 46: ...test for internal data communication Panel for enabling and disabling testing applied to communication data between internal sections of VAC 2006 Press the appropriate numerical key to enable or disa...

Страница 47: ...ollowing option Exit Logout press the OK key The system will return to the Basic Level showing the MUSIC Menu panel The prompt requiring the access password to be entered will also be rein stated for...

Страница 48: ...and customising the system beep SERVICE Connection to the SERVICE menu for technical personnel having the necessary password It is used to change the operating parameters of the VAC 2006 system up da...

Страница 49: ...ION menu Upon completing the procedure carry out a MANUAL RESET of the FAILURE SIGNALLING as described under point 8 5 3 1 page 105 After selecting Acquire IMPEDANCE from the CONFIGURATION menu the AC...

Страница 50: ...vel Press key 6 then turn the knob 5 Line speech lev Voice channel test levels 1 Line 1 level Press key 1 then turn the knob 2 Line 2 level Press key 2 then turn the knob 3 Line 3 level Press key 3 th...

Страница 51: ...rd for accessing the system service levels Use the knob to position the cursor on each digit of the password to be changed Use the numerical keys 1 6 to enter the new password Press OK to enable or di...

Страница 52: ...ress the EMERGEnCY push button again Make sure that you close the lid again B SEndInG An EMERGEnCY SIGnAL FRoM REMotE StAtIonS oF tHE FMd RAnGE Lift the safety lid on the station and press the EMERGEn...

Страница 53: ...n the system will automatically revert to the Idle status displaying the MUSIC menu The ALARM LED will remain OFF to indicate that the VOICE ALARM condition is not active If any alarms from external p...

Страница 54: ...l controls for managing the emergency in order to RESET the messages change the current messages or send live announcements using the microphone provided for this purpose For details about management...

Страница 55: ...t a MANUAL RESET of the failure signal as indicated under point 8 5 3 1 page 105 Note In the event of failure of a loudspeaker line due to a short circuit once the line is repaired it is necessary to...

Страница 56: ...B EMERGENCY UNITS RJ45 for connection to a dedicated emergency microphone station Outputs SLAVE LINK OUTPUT Output level Impedance RJ45 for connection to an VAR 2006 DPU VAIE 2250 unit Max 2000 mV 400...

Страница 57: ...eset of the voice alarm condition 7 9 Voice alarm condition output 8 3 Indication of faluts related to the transmission path 8 4 Indication of faults related to voice alarm zones 9 Disablement conditi...

Страница 58: ...ontrollate tuttavia non si assume nessuna responsabilit per eventuali inesattezze La FBT Elettronica S p A si riserva il diritto di modificare le caratteristiche tecniche ed estetiche dei prodotti in...

Отзывы: