System Manual | 2013
VAIE 2000 | Voice Alarm Integrated Systems
VAC 2006 • VAR 2006
UK
8.1 InItIALISInG tHE SYStEM
The project of the audio system must be implemented with the help of the specific software (see Section 6, “
Configuring the system
”, on page
78).
•
Password
From the HOME page, select the CONFIGURATION menu and press Ok to confirm your choice. If the restriction calling for access with a
password has been enabled, the “CONFIGURATION ACCESS” screen will appear: enter the 4-digit code of the password, then press Ok to
confirm (the default password is
3333
, see page 106).
•
Resetting the BEEP
Failure signals may occur during the initialisation procedure due to the differences between the configuration of the system as connected and the
default settings. To reset the acoustic signal (beep), access the “Report> FAULT” menu and press the RESET key. For details consult “FAULT”
(point 8.5.3.1, page 105)
.
o
Path
: HOME / CONFIGURATION /
report> FAULT (press RESET key).
•
Acquisition of impedances
From the MUSIC menu, set all the outputs with music “OFF”. For details, see “MUSIC menu”
(point 8.2.4, page 90).
Acquire the new loading impedances of the loudspeaker lines, as indicated under “IMP. ACqUISITION” and enable the test by setting the
measurement tolerances.
o
Path
: HOME / CONFIGURATION /
set> TOLERANCE / SET TOLERANCE
o
Path
: HOME / CONFIGURATION /
acquire> IMPEDANCE / IMP. ACqUISITION (press the Ok key)
•
diagnostics for 24 VdC power supply
If the auxiliary 24 VDC power supply has been connected, enable the diagnostic test by setting “24 VDC P.S. ON”, as illustrated under
“BACkGROUND TEST”
(point 8.5.2.3, page 104).
o
Path
: HOME / CONFIGURATION /
set> BACkGROUND TEST / 4-Power supplies
•
Emergency messages
The emergency messages are stored on the SD card using the dedicated software (
see page 83
).
•
Input contacts
Use the dedicated software to programme the input contacts in the appropriate manner on the basis of the Emergency and Evacuation Plan
(E&EP) (
see page 81
).
o
Path
: HOME / CONFIGURATION /
set> CONTROL INPUTS
•
output contacts
Use the dedicated software to programme the output contacts in a suitable manner, on the basis of system specifications, if any (
see page 81
).
o
Path
: HOME / CONFIGURATION /
set> CONTROL OUTPUT
•
Volume control
Adjust the output volume of the Emergency sources suitably so as to ensure that the messages are as intelligible as possible. The level set will
be used for ”Voice Alarm Conditions” and will be the same for all the zones. To adjust the volume of the Emergency Microphone and of the ALERT
and EVAC messages, follow the instructions provided under “ALARM LEVEL”
(point 8.6.4, page 109).
o
Path
: HOME / CONFIGURATION /
set> ALARM LEVEL
•
Resetting failures
Upon completion of the system configuration, the reports concerning failure that have been stored and cleared should be cancelled (RESOLVED).
A FAULT RESET should therefore be carried out as indicated under “FAULTS”
(point 8.5.3.1, page 105).
o
Path
: HOME / CONFIGURATION /
report> FAULT, access the subpanels for viewing failures
•
After initialising the system
After completing the system initialisation procedure, LOG OUT in order to reinstate any access restrictions associated with passwords
(point
8.5.5, page 105).
o
Path
: HOME / CONFIGURATION /
Exit> Logout (press the Ok key).