Advanced Function Instruction
7 -1 2 7
FUN201
D
P
F
Æ
I
CONVERSION OF FLOATING POINT NUMBER TO INTEGER
FUN201
D
P
F
Æ
I
S :
EN
Conversion control
Ladder symbol
201DP.F I
D :
ERR
Range Error
S : Starting register of Integer to be converted
D : Starting register to store the result of conversion
HR
ROR
DR
K
XR
Range
Operand
R0
∣
R383
9
R5000
∣
R8071
D0
∣
D4095
16 bit
OR
32 bit
V
、
Z
P0
~
P9
S
○
○
○
○
D
○
○
*
○
○
Description
z
The format of floating point number of Fatek-PLC follows the IEEE-754 standard. For detail explanation of
the format please refer to 5.3 (Numbering System)…page
5 - 9 .
z
When conversion control "EN" = 1 or "EN
↑
" (
P
instruction) has a transition from 0 to 1, will convert the
floating point data from S~S+1 32bits register into D register( integer data ).
z
If the value exceeds the valid range of destination, then do not carry out this instruction, and set the
range-error flag “ERR” as 1 and the D register will be intact.
X2
EN
201P.F I
R20
S :
D10
D :
ERR