![FATEK FBs Series Скачать руководство пользователя страница 179](http://html1.mh-extra.com/html/fatek/fbs-series/fbs-series_manual_3764826179.webp)
Advanced Function Instruction
7 -1 5
FUN 40
D
P
BITRD
BIT READ
FUN 40
D
P
BITRD
S : Source data to be read
N : The bit number of the S data to be read out.
S, N may combine with V, Z, P0~P9 to serve
indirect address application
WX
WY
WM
WS
TMR CTR
HR
IR
OR
SR
ROR
DR
K
XR
Range
Ope-
rand
WX0
∣
WX240
WY0
∣
WY240
WM0
∣
WM1896
WS0
∣
WS984
T0
∣
T255
C0
∣
C255
R0
∣
R3839
R3840
∣
R3903
R3904
∣
R3967
R3968
∣
R4167
R5000
∣
R8071
D0
∣
D4095
16/32-bit
+/- number
V
、
Z
P0~P9
S
○
○
○
○
○
○
○
○
○
○
○
○
○
○
N
○
○
○
○
○
○
○
○
○
○
○
○
0
~
31
○
z
When read control "EN" = 1 or "EN
↑
" (
P
instruction) changes from 0 to 1, take the Nth bit of the S data
out , and put it to the output bit "OTB".
z
When read control "EN" = 0 or "EN
↑
" (
P
instruction) is not change from 0 to 1, The output “OTB” can be
selected to keep at the last state( if M1919=0 ) or set to zero ( if M1919=1 ).
z
When the operand is 16 bit, the effective range for N is 0~15. For 32 bit operand (
D
instruction) it is 0~31.
N beyond this range will set the N value error flag "ERR" to 1, and do not carry out this instruction.
X0
S :
Y0
EN
40P.BITRD
N : 7
WX 0
OTB
ERR
z
The instruction at left reads the 7th bit (X7) status from
WX0 (X0~X15) and output to Y0. The results are as
follows:
X15
X7
X0
S
WX0 1 1 0 0 1 1 1 0 1 0 0 1 1 0 0 1
N
=
7
──────────
Ø
X0
=
Y0
1
Содержание FBs Series
Страница 78: ...MEMO ...
Страница 111: ...4 6 X0 X1 Node A Y0 Y1 Node B differential down Incerse differential up t Scan time Inverse t t ...