Advanced Function Instruction
7 -8 2
FUN 95
RAMP
RAMP
FUNCTION
FOR D/A OUTPUT
FUN 95
RAMP
Program example
M0
EN
Tn : T20
ERR
M100
PV : R100
S
L
:
D :
S
U
:
M1
PAU
M2
U/D
ASL
M101
ASU
R101
R102
R103
M102
M0
EN
8.MOV
D : R3904
S : R103
95.RAMP
Move the ramping value to AO output register
R3904
T20: Ramp timer (timer with 0.01 second time base)
R100: preset value of ramp timer (the unit is 0.01 second, 100 for a second).
R101: Lower limit value.
R102: Upper limit value.
R103: Register storing current ramp value.
R104: Working register
z
If M1974=0, When input control M0 changes from 0
→
1, it first reset the timer T20 to 0. If M2=1, it will load
the R101 (lower limit) value into the R103, and it will increase the output with fixed value (R102-R101 / R100)
for every 0.01 second and stores it to register R103. When the T2 timer going up to the preset value R100,
the output value equals to R102, and the output M102 will set to 1. If M2=0, will load the R102 (upper limit)
value into the R103, and it will decrease the output amount with fixed ratio (R102-R101 / R100) for every 0.01
second and store it to register R103. The T2 timer going up to the preset value R100, the output value equals
to R102, and the output M101 will set to 1.
z
M1=1, pause the ramping action.
z
The value of R102 must be greater than R101, otherwise the ramp action will not be performed, and the
output M100 will set to 1.
S
U
S
L
PV
PV
t