Supervisory Indications
Individual fire panel supervisory conditions will be transmitted to the RND-2s and network printers.
All initiating devices on the MPC-6000 or MPC-7000 can also be programmed to a network LINK (accomplished while
configuring devices on the panel). The maximum LINK number for the MPC-6000 and MPC-7000 is 255. If an
initiating device on a panel goes into supervisory, and it has been programmed to a network LINK, it will send a
network message to the other panels indicating that the network LINK is in supervisory. If other panels on the network
have that LINK number programmed, they will indicate the supervisory as configured.
Other panels will display:
Explanation of display/history event:
SUP xxx/yyy 10:12
40 character custom
link message
NN:L175 NETWORK LINK
This is x of y supervisories in the system that was logged at 10:12 (24 hour
time)
These two lines will indicate a custom message for the network link
Bottom line indicates that node link 175 on node nn is the source of the
trouble. The plus sign at the end indicates that there are more
RND-2s will display:
Explanation of display/history event:
SUP xxx/yyy 10:12
40 character custom
link message
NN:xxxx Device type
The RND-2 if configured for this will also show the individual point information.
Other panels will display:
Explanation of display/history event:
R/SUP xxx/yyy 10:12
40 character custom
link message
NN:L175 NETWORK LINK
This is the restoral of x of y supervisories in the system that was logged at
10:12 (24 hour time)
These two lines will indicate a custom message for the network link
Bottom line indicates that node link 175 on node nn is the source of the
trouble. The plus sign at the end indicates that there are more
RND-2s will display:
Explanation of display/history event:
R/SUP xxx/yyy 10:12
40 character custom
link message
NN:xxxx Device type
The RND-2 if configured for this will also show the individual point information.
Alarms Indications
Individual fire panel alarms will be transmitted to the RND-2s and network printers.
All initiating devices on the MPC-6000 or MPC-7000 can also be programmed to a network LINK (accomplished while
configuring devices on the panel). The maximum LINK number for the MPC-6000 and MPC-7000 is 255. If an
initiating device on a panel goes into alarm, and it has been programmed to a network LINK, it will send a network
message to the other panels indicating that the network LINK is in alarm. If other panels on the network have that
LINK number programmed, they will operate as configured.
Other panels will display:
Explanation of display/history event:
ALM xxx/yyy 10:12
40 character custom
link message
NN:xxxx Device type
This is x of y troubles in the system that was logged at 10:12 (24 hour time)
These two lines will indicate a custom message for the network link
Bottom line indicates that node link 175 on node nn is the source of the
trouble. A plus sign at the end indicates that there are more
RND-2s will display:
Explanation of display/history event:
ALM xxx/yyy 10:12
40 character custom
link message
NN:xxxx Device type
The RND-2 if configured for this will also show the individual point information.
firealarmresources.com
Содержание MPC-NET2
Страница 2: ...P N 315 049594 1 2 This page is intentionally blank firealarmresources com...
Страница 4: ...P N 315 049594 1 4 firealarmresources com...
Страница 10: ...P N 315 049594 1 10 firealarmresources com...
Страница 14: ...P N 315 049594 1 14 firealarmresources com...
Страница 15: ...P N 315 049594 1 15 firealarmresources com...
Страница 18: ...P N 315 049594 1 18 99 firealarmresources com...
Страница 22: ...P N 315 049594 1 22 firealarmresources com...
Страница 23: ...P N 315 049594 1 23 firealarmresources com...
Страница 24: ...P N 315 049594 1 firealarmresources com...