P/N 315-049594-1 

5

 

I. FARADAY 

MPC-NET2 

INTRODUCTION 

The Faraday MPC-NET2 network is a way to link MPC-6000 or MPC-7000 Fire Alarm Control units, RND-2 Remote 
Network Displays and printers together to form a network.  MPC-6000 and MPC-7000 Firmware version 3.0 or higher 
is required to be running on each panel.  A total of 99 Network Interface Boards (NIBs) can be connected on a 
network. 

INSTALLATION 

Network Wiring 

Network wire is to be UL listed Category 5 or better cable, rated for the type of installation.  The network is wired from 
node to node in a daisy chained ring configuration for Style 7 operation.  The network side of the NIB has 2 ports.  
Port 1 (reverse direction) is an isolated port and port 2 (forward direction) is a non-isolated port.  Port 2 of a NIB must 
be wired to port 1 of the next NIB.  The network signals are regenerated at each NIB allowing a maximum distance of 
3000’ between NIBs when using Category 5 wire.  The NIB must be mounted in the same room as the RS232 serial 
device it is connecting to.  All panel to NIB wiring is to be in conduit. 
 
If the NIB is connected to a NIB in another building using Category 5 wire, each of those 2 NIBs requires an inline 
12525-surge protector to meet National Electrical Code requirements. 
Refer to the installation and wiring diagrams for more details. 

 

Fiber Converters 

It is possible to convert one or both of the network ports of an “A” version NIB to use fiber media instead of Category 
5 wire with the use of optional fiber converters 12535 or 12536.  Each converter converts one port of the NIB to fiber 
media. There is a converter for single mode fiber and one for multimode fiber. The converters plug directly into 
sockets onto the NIBs.  Different media types can be mixed on the same NIB.  A maximum of 2 media types can be 
used per NIB. 
The multimode converter 12535 is designed to use duplex 62.5/125 

µ

m multi-mode fiber cable with ST connectors. 

The single mode converter 12536 is designed to use duplex 9/125 

µ

m single mode fiber cable with SC connectors.  

The maximum loss allowed between each NIB with fiber converters is 10dB. 

 

NIB Versions 

The NIB communicates with the attached device it is connected to through an RS232 port.  The NIB must also be 
powered by a MPC-6000, MPC-7000 or RND-2 for 24VDC. 
There are three versions of NIBs.  

1).  12523A is a NIB designed to connect to a serial port on an MPC-6000, MPC-7000 or RND-2. 
2).  12526A is a NIB with an isolated RS232 port. It is designed to connect to printers and any computers on 

the network. 

3).   12603A is a NIB designed to connect to a serial port on an MPC-6000 or MPC-7000 and mount inside the 

cabinet.  It is electrically the same as a 12523A. 

Note: Each piece of equipment connected to the network requires a NIB. 
 

NIB Current Draws 

NIB Part No. 

Alarm 

Stand By 

Converter Part No. 

Alarm 

Stand By 

12523A 

.085 A. 

.085 A. 

12535 

.120 A. 

.120 A. 

12526A 

.085 A. 

.085 A. 

12536 

.100 A. 

.100 A. 

12603A 

.085 A. 

.085 A. 

 

 

 

 
 

firealarmresources.com

Содержание MPC-NET2

Страница 1: ...Inc 8 Fernwood Road Florham Park NJ 07932 Tel 973 593 2600 Fax 973 593 6670 Web www faradayfirealarms com P N 315 049594 1 MPC NET2 MPC Net System Networking Owner s Manual 315 049594 Revision 1 0 03...

Страница 2: ...P N 315 049594 1 2 This page is intentionally blank firealarmresources com...

Страница 3: ...le indications 7 Supervisory Indications 8 Alarms Indications 8 II NETWORK ANNUNCIATORS 9 RND 2 9 III NETWORK TROUBLESHOOTING 11 NIB LED INDICATORS 11 NETWORK SPECIFIC TROUBLES 12 IV WIRING DIAGRAMS 1...

Страница 4: ...P N 315 049594 1 4 firealarmresources com...

Страница 5: ...both of the network ports of an A version NIB to use fiber media instead of Category 5 wire with the use of optional fiber converters 12535 or 12536 Each converter converts one port of the NIB to fibe...

Страница 6: ...2 Send global commands 1 yes 0 no For RND 2 only The NIB configuration data is passed from the panel to the NIB at power up and reset of the panel Printer NIB Configuration For wiring connections ref...

Страница 7: ...es in the system that was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trou...

Страница 8: ...hat was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trouble The plus sign...

Страница 9: ...bally or for the RND 2 only Alarms may also be silenced globally The RND 2 has the ability to reset all panels on the network or just the RND 2 There is also a network event history that can be retrie...

Страница 10: ...P N 315 049594 1 10 firealarmresources com...

Страница 11: ...e FA panel or annunciator It should blink every couple of seconds when the NIB is connected to a FA panel or annunciator If the NIB is connected to a printer this LED will only blink when data is bein...

Страница 12: ...nel showing this message is not communicating with its NIB NW Ring Broken The network is not physically in tact NW Forward Link Port 2 of the attached NIB has lost the link with port 1 of the next NIB...

Страница 13: ...e installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Category 5 wire with...

Страница 14: ...P N 315 049594 1 14 firealarmresources com...

Страница 15: ...P N 315 049594 1 15 firealarmresources com...

Страница 16: ...t be daisy chained from network interface board to network interface board 3 Use Category 5 wire with 3000 feet maximum distance from network interface module to network interface module Step 1 Instal...

Страница 17: ...otes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Cate...

Страница 18: ...P N 315 049594 1 18 99 firealarmresources com...

Страница 19: ...mounts inside the MPC 6000 cabinet Notes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board...

Страница 20: ...r printers as described earlier in the wiring diagram section 3 Attach Duplex fiber to Converter using the ST connectors on the Converter For the 12536 Single Mode Converter 1 Install on NIB carefully...

Страница 21: ...event the output coding may be selected Local Panel Output Zone mapping MPC 6000 7000 panel up to 99 panels Group XX Up to Group 240 T 22 1 32 12 U U U U C T Input group 1 Group 2 Local Panel Output Z...

Страница 22: ...P N 315 049594 1 22 firealarmresources com...

Страница 23: ...P N 315 049594 1 23 firealarmresources com...

Страница 24: ...P N 315 049594 1 firealarmresources com...

Отзывы: