background image

 

P/N 315-049594-1 

13

 

IV. WIRING DIAGRAMS 

12523A NETWORK INTERFACE BOARD 

The 12523 or 12523A Network Interface Board is a module to interface between the MPC-6000 or MPC-
7000 Fire Alarm System Control Unit or the RND-2 Remote Network Display. The NIB mounts to a 6-
gang box, 2” deep minimum.  The Faraday 12411 surface backbox or the 12525 surface backbox with 
transient suppressor may be used for surface mounting. 

 

 
 

12523 / 12523A Dimensions

12525 Dimensions

 

12523 / 12523A Wiring

 
Notes: 
 
1.) 

Units to be installed in accordance with all local codes. 

2.) 

T-Tapping is not allowed.  Communication wiring must 

          be daisy chained from network interface board to    
          network interface board. 
3.)      Use Category 5 wire with 3000 feet maximum distance 
          from network interface module to network interface 
          module. 
4.) 

12525 is required when network wiring leaves the  

 building. 

FROM PREVIOUS

FROM PREVIOUS

NIB

TO NEXT NIB

TO NEXT NIB

FRAME GROUND

FRAME GROUND

FROM MPC-6000 OR

MPC-7000 FIRE

ALARM CONTROL

PANEL OR RND-2

FROM MPC-6000 OR

MPC-7000 FIRE

ALARM CONTROL

PANEL OR RND-2

TO MPC-6000 OR

MPC-7000 FIRE

ALARM CONTROL

PANEL OR RND-2

TO MPC-6000 OR

MPC-7000 FIRE

ALARM CONTROL

PANEL OR RND-2

firealarmresources.com

Содержание MPC-NET2

Страница 1: ...Inc 8 Fernwood Road Florham Park NJ 07932 Tel 973 593 2600 Fax 973 593 6670 Web www faradayfirealarms com P N 315 049594 1 MPC NET2 MPC Net System Networking Owner s Manual 315 049594 Revision 1 0 03...

Страница 2: ...P N 315 049594 1 2 This page is intentionally blank firealarmresources com...

Страница 3: ...le indications 7 Supervisory Indications 8 Alarms Indications 8 II NETWORK ANNUNCIATORS 9 RND 2 9 III NETWORK TROUBLESHOOTING 11 NIB LED INDICATORS 11 NETWORK SPECIFIC TROUBLES 12 IV WIRING DIAGRAMS 1...

Страница 4: ...P N 315 049594 1 4 firealarmresources com...

Страница 5: ...both of the network ports of an A version NIB to use fiber media instead of Category 5 wire with the use of optional fiber converters 12535 or 12536 Each converter converts one port of the NIB to fibe...

Страница 6: ...2 Send global commands 1 yes 0 no For RND 2 only The NIB configuration data is passed from the panel to the NIB at power up and reset of the panel Printer NIB Configuration For wiring connections ref...

Страница 7: ...es in the system that was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trou...

Страница 8: ...hat was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trouble The plus sign...

Страница 9: ...bally or for the RND 2 only Alarms may also be silenced globally The RND 2 has the ability to reset all panels on the network or just the RND 2 There is also a network event history that can be retrie...

Страница 10: ...P N 315 049594 1 10 firealarmresources com...

Страница 11: ...e FA panel or annunciator It should blink every couple of seconds when the NIB is connected to a FA panel or annunciator If the NIB is connected to a printer this LED will only blink when data is bein...

Страница 12: ...nel showing this message is not communicating with its NIB NW Ring Broken The network is not physically in tact NW Forward Link Port 2 of the attached NIB has lost the link with port 1 of the next NIB...

Страница 13: ...e installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Category 5 wire with...

Страница 14: ...P N 315 049594 1 14 firealarmresources com...

Страница 15: ...P N 315 049594 1 15 firealarmresources com...

Страница 16: ...t be daisy chained from network interface board to network interface board 3 Use Category 5 wire with 3000 feet maximum distance from network interface module to network interface module Step 1 Instal...

Страница 17: ...otes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Cate...

Страница 18: ...P N 315 049594 1 18 99 firealarmresources com...

Страница 19: ...mounts inside the MPC 6000 cabinet Notes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board...

Страница 20: ...r printers as described earlier in the wiring diagram section 3 Attach Duplex fiber to Converter using the ST connectors on the Converter For the 12536 Single Mode Converter 1 Install on NIB carefully...

Страница 21: ...event the output coding may be selected Local Panel Output Zone mapping MPC 6000 7000 panel up to 99 panels Group XX Up to Group 240 T 22 1 32 12 U U U U C T Input group 1 Group 2 Local Panel Output Z...

Страница 22: ...P N 315 049594 1 22 firealarmresources com...

Страница 23: ...P N 315 049594 1 23 firealarmresources com...

Страница 24: ...P N 315 049594 1 firealarmresources com...

Отзывы: