MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
16
GENERAL SPECIFICATIONS
Operating specifications for the MPC-6000 / MPC-7000 / RND-2 are as follows:
Environmental
•
Operating temperature - 32 - 120
°
F (0 - 49
°
C)
•
Relative humidity - Up to 85% @ 86
°
F (30
°
C)
Primary Supply
•
Primary Input Voltage: 120 VAC (60 Hz) nominal
•
MPC-6000 / RND-2 Maximum primary input current: 2.4A at 120 VAC
•
MPC-7000 Maximum primary input current: 3.2A at 120 VAC
Secondary and Trouble Power Supply
•
24 volt lead-acid battery set
•
Maximum Charge Voltage: 27.8 VDC
•
Automatic Low Battery Disconnect - Disconnect Voltage: 18VDC
•
MPC-6000 / RND-2 Maximum Charge Current: 1.7A
•
MPC-7000 Maximum Charge Current: 3.8A
•
MPC-6000 / RND-2 Battery capacity: 7-38.5 AH (over 12 AH requires separate enclosure
for the batteries)
•
MPC-7000 Battery capacity: 7-38.5 AH / 100 AH with optional Battery Charger, HBC-1
(over 18 AH requires separate enclosure for the batteries)
Auxiliary Power Outputs
•
0.4 amp maximum per power output circuit
MPC-6000 / RND-2 0.5 amp total / MPC-7000 1.0 amp maximum available for auxiliary
power output circuits, Serial Interface Circuits and option boards
•
Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
•
Resettable
Power
Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Status Relays
Four relays programmable for alarm, supervisory, trouble, loss of AC.
•
Contact
Rating:
1 A, 28 VDC maximum, resistive
•
Form C Contact