MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
12
X1 ADDRESSABLE DEVICES
Fire Smart™ Smoke Detector
The control unit processor sends the sensitivity and pre-alarm settings to the detectors and
polls the detectors as to their status. The detector determines normal, trouble, pre-alarm or
alarm conditions and communicates the status to the control unit.
•
Variable Thesholds - The detectors can be set to operate in various pre-programmed
optimizations, depending on installation locations.
•
Operator Alerts - The control unit can trigger an alarm or trouble automatically on the
occurrence of a number of conditions of the detector. These include:
Maintenance alert
Pre-alarm alert
No response
Incorrect response
Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where heat
sensing may be the most effective detection mode. The heat detectors may be programmed,
through the control unit, for rate of rise operation.
Addressable Modules (Monitor and Control)
In addition to detectors, the circuit can communicate with addressable modules, allowing
initiating devices or notification appliances with local power sources, and supervising the
power sources.
Manual Stations
Addressable manual stations may be intermixed on the circuit with proper response
programmed into the control unit.
Programming X1 Devices
X1 devices can be programmed in the following manner:
•
8720 Device Programmer/ Loop Tester - Refer to the 8720 User’s Manual, P/N 315-
033260FA, for further information.
•
MPC-6000 / MPC-7000 / RND-2 Panel Keypad – Refer to the MPC-6000 / MPC-7000 /
RND-2 Programmer’s Manual, P/N 315-049403FA, for detailed information of system
programming. Used only for field removal and reinstallation of individual devices.