MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
10
OPTIONAL MODULES
CT-1K City Tie Board (MPC-6000 / MPC-7000 / RND-2)
The Faraday CT-1K city tie board provides local energy and polarity reversal connections. The
polarity reversal connections provide a trouble circuit and an alarm circuit with optional trouble
output. The CT-1K mounts onto the main termination board. (Cannot be used in conjunction
with a DACT Board).
MPC-DACT DACT Board (MPC-6000 / MPC-7000 / RND-2)
The Faraday MPC-DACT Digital Alarm Communication Transmitter board will send control unit
status data to a remote receiving station. The MPC-DACT mounts onto the main termination
board (Cannot be used in conjunction with the City Tie Board).
NPE-1 Transformer Assembly (MPC-6000 / MPC-7000)
The Faraday NPE-1 optional transformer assembly provides an additional 3 amps of NAC
power. The transformer mounts in the cabinet above the two transformers that come standard
with the MPC-6000 / MPC-7000. A maximum of one optional NPE-1 is allowed per system.
NEM-1 NAC Expansion Board (MPC-7000)
The NEM-1 NAC Expansion Board has eight independent Class B (Style Y) notification
appliance circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation.
This reduces the number of NACs to four. Each circuit can be selected to give continuous
output or one of eight sounding patterns available in the control unit including the Faraday
SYNC Protocol. There is also a system coder capable of zone-coded operation. All of the
NACs are power limited. Maximum of one NAC Expander board per MPC-7000 system.
LEM-1 Loop Expander Board (MPC-7000)
The LEM-1 has circuitry for the addition of an additional two FDLC Loop Driver boards to a
MPC-7000 panel. (FDLC Loop Driver Boards are not included). A maximum of one Loop
Expander Board is allowed per MPC-7000 system.
FDLC Loop Driver Board (MPC-7000)
The FDLC has one addressable device circuit that is programmed for connection to Faraday
addressable devices using the X1. The circuit has the capacity for 252 addresses. A maximum
of four FDLC boards per MPC-7000 panel is allowed. (Loops 3 and 4 require a LEM-1 Loop
Expander Board.)
HBC-1 Battery Charger (MPC-7000)
The HBC-1 is an optional battery charger to increase the charging capacity of the MPC-7000
to 100AH lead acid batteries.
Battery Sets
The MPC-6000 / MPC-7000 / RND-2 control units are designed to use only sealed lead-acid or
equivalent batteries for back-up power. Attaching a close-coupled battery box, if required, may
allow use of battery sets beyond the physical capacity of the enclosure (12AH for the MPC-
6000 and 18AH for the MPC-7000). Maximum battery charging capacity for the MPC-6000 is
38.5AH. Maximum battery charging capacity for the MPC-7000 is 38.5AH. (100AH with the