M P C 6 0 0 0 / 7 0 0 0 P R O G R A M M I N G M A N U A L
25
investigation phase. If the signal is not acknowledged within 15
seconds a general alarm will sound.
The investigation phase can last up to 180 seconds. If the system is
not reset during this period a general alarm will sound.
If a second PAS alarm occurs during the investigation phase the
general alarm will sound.
Pre-Signal Pre-signal
as
defined by NFPA allows initial Fire Alarm signals to
sound only in department offices, control rooms, fire brigade stations
or other constantly attended central locations for which human action
is subsequently required to activate general alarm or a feature that
allows the control equipment to delay the general alarm by more than
1 minute after the start of alarm processing. Where there is a
connection to a remote location, it shall activate upon the initial alarm
signal.
Wild Card
Wild Card zone for non-fire operation allows monitoring of critical
functions with logging or control function. The event will latch and will
not reset until the panel is reset.
The coding of the bells for alarm, trouble, supervisory and pre-alarm events may be
selected for each input group from Steady on, March time, Temporal, California, 3-
Pulse Temporal and Alert.
An input Group may also be configured to activate 1 or all of the 255 Output Zones.
Editing a System Group Configuration
There are a number of system groups, which may be configured as follows:
Select
“Edit”.
Select
“Manual
Pgm”.
Select
“Groups”.
Select
“System
Groups”.
Select the system
group to be edited.
The user may now
navigate through
screens which allow
setting the bell codes
that the system group
will use and the outputs
which this system group
will activate.
Configuring the NACs
There are a number of parameters that may be configured for the NACs.
Select
“Edit”.
Select
“Manual
Pgm”.
Select
“Outputs”.
Select
“NACs”.
Enter the number of
the NAC to be
configured.
The user may now
navigate through
screens that allow
setting the parameters of
the NACs.