M P C 6 0 0 0 / 7 0 0 0 P R O G R A M M I N G M A N U A L
18
Enabling/Disabling NACs
The Notification Appliance Circuits may be disabled/enabled as follows:
Press
“Disable/Enable”.
Press “Outputs”.
Press “NACs”.
Enter the number of
the NAC through
the keypad and
press “Enter”. The
display will show
the current state of
the NAC.
Use the
“Enable(Disable)”
button to change
the state of the
NAC. Status will
toggle on the
display.
Enabling/Disabling City Tie
The City Tie Circuit may be disabled/enabled as follows:
Press
“Disable/Enable”.
Press “Outputs”.
Press “More” and
then press “City
Tie”.
The display will
show the status of
the City Tie.
Use the
“Enable(Disable)”
button to change
the state of the City
Tie. Status will
toggle on the
display.
Enabling/Disabling the DACT
The DACT (Digital Alarm Communication Transmitter) may be disabled/enabled as
follows:
Press
“Disable/Enable”.
Press “Outputs”.
Press “More” and
then press “DACT”.
The display will
show the status of
the DACT.
Use the
“Enable(Disable)”
button to change
the state of the
DACT. The Status
will toggle on the
display.
Enabling/Disabling the Status Relays
The Status Relays may be disabled/enabled as follows:
Press
“Disable/Enable”.
Press “Outputs”.
Press “More”, press
“More” and then
press “Status
Relays”.
The display will
show the status of
the Status relays.
Use the
“Enable(Disable)”
button to change
the state of the
Status Relays. The
status will toggle on
the display.