M P C 6 0 0 0 / 7 0 0 0 P R O G R A M M I N G M A N U A L
11
The basic concept is that loop devices are configured and grouped into input groups.
The input groups are set to have a certain behavior and activate output zones. The
output devices
―
whether relay bases, audible bases, NACs, serial LEDs or Serial
relays
―
are configured and connected to Output Zones.
Automatic Programming
Auto-program can be done with a new, non-configured control unit or to augment an
existing configuration. Augmenting an existing program adds new points but leaves
previously programmed points unaffected. Discrepancies in the configuration will be
presented individually for acceptance. Again, auto program writes information into
the backup and must be validated before becoming the primary operating
configuration.
Auto Program will recognize the types of devices connected and will set up different
parameters depending on the devices it finds. The following tables show the settings
for the different device types.
Smoke and thermal detectors
Parameter
Description
Label
Generic label identifying the detector by loop number and address.
Application
If FireSmart detectors are found, the application will not be changed in the
device. Factory default is none.
Sensitivity
The sensitivity of the detectors will be left as found. The factory default is
3.00%.
ROR
Rate of rise will be off.
Led off
LED will be defaulted to ON.
Pre-alarm
Pre-alarm will be off.
Verification
Verification will be as found in the detector.
Input Usage
The input usage will be set to Alarm.
Input Group
All detectors will be set to input group 241.
Network Group
This will not be set and will need to be set manually. (Future use)
Relays and
Audible bases
Will be set for auto activation. The relay or audible base will activate
when the device activates.
Monitor Modules, Manual Stations and Conventional Zone modules
Parameter
Description
Label
Generic label identifying the detector by loop number and address.
Led off
LED will be defaulted to ON.
Input Usage
Input usage will be set to alarm.
Input Group
All inputs will be set to input group 241.
Network Group
This will not be set and will need to be set manually. (Future use)