M P C   6 0 0 0 / 7 0 0 0   P R O G R A M M I N G   M A N U A L  

Note 

NOTE #1: The backup configuration will now contain a configuration as follows: 
all input points in group #241 (General Alarm). The General Alarm System 
group is pre-programmed to activate all output zones. Any Remote LCD 
displays that were connected at the time of Auto Program will also be activated. 
However remote relay (SRUs) and remote Led modules (SLUs) will not be 
detected and so will not be in the configuration. 

4 At 

the 

EDIT BACKUP

 screen, press 

“A”

 

and escape back to 

TECH LEVEL

 

screen. 

The display will show the starting 
technician menu. 

Use “C” to get to the next set of functions 
and select “validate”. 

This will cause the data in the 
backup configuration to be 
checked. Correct any errors found 
before continuing. 

Press the “

*

” key followed by the "

C

" key 

when prompted. This action will cause the 
auto programmed configuration to be 
swapped into the primary memory and the 
panel will be restarted. (You now have as 
the primary configuration the result of the 
Auto Program. In other words, a General 
Alarm system.) 

The panel will reset and reinitialize. 

 
 
 
 
 

Manual programming of a system 

 
Manual programming is a much more involved operation and requires knowledge of 
the operation of the system before proceeding. The basic steps to programming a 
system configuration are as follows: 
 

Step Number 

Configure 

Description 

System configuration  Set a number of overall system parameters. 

Loops 

Set up each loop, one in the case of the 6000 
and (up to) four in the case of the 7000. 

3 Input 

groups/system 

groups  

Set up the behavior of the input group or system 
groups--the bell codes it will activate and the 
output zones that will be activated by this input 
group. Note that an input group must be 
configured to activate an output group to cause 
any output activations. 

Devices  

Set the address and other parameters for each 
of the devices that will be installed into the 
system. Configure the input group of each 
device. Note that devices must be connected to 
an input group for any output to be activated. If 
the panel is networked, also setup the network 
group that this device will activate. 

Содержание MPC-6000

Страница 1: ...FARADAY 8 Fernwood Road Florham Park New Jersey 07932 P N 315 049403FA 1 MPC 6000 MPC 7000 Fire Alarm System Control Unit Programming Manual...

Страница 2: ......

Страница 3: ...vating a General Alarm 14 Activating an Alert 14 Activating a Drill 14 Activating a Recall 15 Performing a Lamp Test 15 Viewing the Event History 15 Accessing Maintenance Functions 15 Accessing Techni...

Страница 4: ...Group Configuration 25 Configuring the NACs 25 Configuring the Remote Relays SRUs 26 Configuring the Remote LEDs SLUs 26 Configuring the Remote LCDs RDCs 27 Installing the DACT 27 Configuring the DACT...

Страница 5: ...d running quickly The Access levels The MPC 6000 7000 system has three functional levels as follows User Level no password is required to access these functions Maintenance Level accessed using the Ma...

Страница 6: ...password Program a device Clear event history Enabling or disabling application Technician Level The Technician level is accessed via the User Menu and entering the correct password The functions acce...

Страница 7: ...in the four corners of the display that will be adjacent to the four buttons M1 through M4 The message on the display adjacent to the button indicates the action that will occur when the button is pr...

Страница 8: ...g The following figure describes the navigation used in this context A esc will backup to previous screen B fn1 will perform function 1 C fn2 will perform function 2 D Nxt will step to the next screen...

Страница 9: ...and Z which do not appear on the keypad The letter Q is entered using the sequence 27 as though Q appears on the 7 between P and R The letter R is entered as 37 and S as 47 Similarly Z is entered as 4...

Страница 10: ...ssword 3 Enter the password on the keypad The default is 0 1 2 3 4 5 The password will appear in the screen 4 Press Enter or D The display will show the starting screen of the Technician Level Once th...

Страница 11: ...as the primary configuration the result of the Auto Program In other words a General Alarm system The panel will reset and reinitialize Manual programming of a system Manual programming is a much mor...

Страница 12: ...Optional 7 Remote LEDs If there are any remote LED modules configure each of the remote LEDs Select the Output zone that will activate the LED Optional 8 Remote Relays If there are any remote Relay mo...

Страница 13: ...lly Before the backup configuration is activated it first must be validated to make sure that the configuration follows the installation rules The validation process ensures no values or operating par...

Страница 14: ...waterflow trouble supervisory non fire panel reset alarm silence acknowledge Each relay can have its output behavior configured i e non silencable trouble active supervisory pre alarm silenceable trou...

Страница 15: ...e types Smoke and thermal detectors Parameter Description Label Generic label identifying the detector by loop number and address Application If FireSmart detectors are found the application will not...

Страница 16: ...tion Label Generic label identifying the detector by loop number and address Output Type Will be set to non silenceable Output Zone Will be set to 1 NACs Parameter Description Notification Device Type...

Страница 17: ...in auto program The following devices cannot be detected automatically Bell Codes Serial Remote Processor LEDs Serial Remote Processor Relays DACT City Tie Programming of these points is not changed b...

Страница 18: ...n of the General Alarm Press Yes to activate a General Alarm The display will return to normal indicating General alarm has been activated Press System Reset or Alarm Silence to stop Activating an Ale...

Страница 19: ...t History The Event History screen displays the last 2000 events reported to a panel The information displayed includes the date and time the type of event TRB ALM SUP etc the device reporting the eve...

Страница 20: ...s available after the technician password has been entered Follow the steps below to access the technician functions Press Menu and press More three times Press Tech Menu The display will show the scr...

Страница 21: ...status of the group will be displayed Use the Enable Disable button to change the state of the group Status will toggle on the display Enabling Disabling Applications The applications in the FireSmar...

Страница 22: ...e status of the City Tie Use the Enable Disable button to change the state of the City Tie Status will toggle on the display Enabling Disabling the DACT The DACT Digital Alarm Communication Transmitte...

Страница 23: ...ime format Use the 12 hour 24 hour buttons to set the time format Enabling Daylight Savings Time Adjustment The MPC 6000 and 7000 can adjust for daylight savings automatically Follow the steps below t...

Страница 24: ...ollowing steps Press More then press Print Hist The display will show the Print Fwd and Print Reverse options Select the direction of printing that is desired The display will show a message that hist...

Страница 25: ...he NACs will sound during Quick Test Use the Inc and Dec buttons to set the time either to off or from 1 to 30 seconds Configuring the printer during Quick Test Printing may be enabled or disabled dur...

Страница 26: ...addressed using a four digit address The first left most digit is the loop number while the next three digits specify the address on the loop The setup of an input device will vary depending on the ty...

Страница 27: ...e following table provides a description of the parameters that may be set for each device Parameter Description Label Each device may have a forty character label assigned to it to describe the input...

Страница 28: ...action Editing an Input Group Configuration An input group s configuration may be edited as follows Select Edit Select Manual Pgm Select Groups Select Input Groups Key in the input group number The us...

Страница 29: ...zone for non fire operation allows monitoring of critical functions with logging or control function The event will latch and will not reset until the panel is reset The coding of the bells for alarm...

Страница 30: ...he parameters of the address relay The relays in the serial relay unit must be logically connected to an output zone in order to operate When the selected output zone becomes active the relay will bec...

Страница 31: ...are the steps that need to be followed to configure the remote LED units Select Edit Select Manual Pgm Select Outputs Use Cmor and select Option Mods Select DACT ACCTS Follow the screen prompts to set...

Страница 32: ...press Bsav Setting Trouble Ack Required Troubles and supervisory events are normally self restoring however if it is required that they need to be acknowledged before clearing follow the procedure bel...

Страница 33: ...lay will indicate that the validity check is running Display will show invalid settings in the configuration if found Activating the Backup When the configuration is correct it may be made the primary...

Страница 34: ...0 P R O G R A M M I N G M A N U A L 30 Exiting the Technician Level Follow the steps below to exit the Technician level and return to User level Use Cmor and select Exit Tech LvL The Display will retu...

Страница 35: ...em Audible Signal A sound made by one or more audible notification appliances such as bells or horns in response to the operation of an initiating device Authority Having Jurisdiction AHJ The organiza...

Страница 36: ...for instance the first floor Labeled Equipment or materials to which have been attached a label symbol or other identifying mark of an organization acceptable to the authority having jurisdiction and...

Страница 37: ...g to the test mode of the system that automatically resets after a service tech tests initiating devices Supervisory Alarm A signal indicating the operation of a supervisory device Supervisory Device...

Страница 38: ...onal Fire Alarm Code National Fire Protection Association NFPA 70 National Electrical Code Delmar Publishers MPC 6000 Faraday Fire Alarm Control Panel Owner s Manual manual P N 315 447309 1 Faraday we...

Страница 39: ......

Страница 40: ...FARADAY 8 Fernwood Road Florham Park New Jersey 07932 P N 315 049403FA 1...

Отзывы: