UL Compatible Two-Wire (Circuit Powered) Smoke & Heat Detectors
Zone Identifier – H for 12503 Conventional Expansion Board
Faraday
Detector
w/Base
Mfg.
Detector
w/Base
Number of
Detectors
Per Circuit
Maximum
Standby
Current
Detector
Identifier
Base
Identifier
Air Products & Controls
9267
RW-2W-N
0-30
0.081mA
RW-2WN
45681-200
9268
RW-2W-P
0-27
0.110mA
RW-2WP
45681-200
Apollo Fire Detectors
9260 w/9262
55000-350 w/45681-220
0-27
0.110mA
55000-350
45681-220
9260 w/9265
55000-350 w/45681-230
0-23
0.130mA
55000-350
45681-230
9261 w/9262
55000-250 w/45681-220
0-30
0.081mA
55000-250
45681-220
9261 w/9265
55000-250 w/45681-230
0-30
0.100mA
55000-250
45681-230
9264 w/9262
55000-153 w/45681-220
0-30
0.057mA
55000-153
45681-220
9264 w/9265
55000-153 w/45681-230
0-30
0.057mA
55000-153
45681-230
9274 w/9262
55000-152 w/45681-220
0-30
0.057mA
55000-152
45681-220
9274 w/9265
55000-152 w/45681-230
0-30
0.089mA
55000-152
45681-230
Faraday, LLC
8842 w/8853
8842 w/8853
0-27
0.110mA
8842
8853
8842 w/8853 (5)
8842 w/8853
(5)
0-13
0.220mA
8842
8853
8843 w/8853
8843 w/8853
0-27
0.110mA
8843
8853
8843 w/8853 (5)
8843 w/8853
(5)
0-13
0.220mA
8843
8853
8854 w/8853
8854 w/8853
0-27
0.110mA
8854
8853
8854 w/8853 (5)
8854 w/8853
(5)
0-13
0.220mA
8854
8853
8854 w/8840
8854 w/8840
0-27
0.110mA
8854
8840
8854 w/8840 (5)
8854 w/8840
(5)
0-13
0.220mA
8854
8840
System Sensor
9184 w/9185
1151 w/B110LP
0-25
0.120mA
A
A
9183 w/9185
2151 w/B110LP
0-25
0.120mA
A
A
8434
2100S
0-25
0.120mA
A
---
8415
2100TS
0-25
0.120mA
A
---
8423
DH100P
0-25
0.120mA
A
---
9374
1400
0-25
0.120mA
A
---
9375
2400
0-25
0.120mA
A
---
9376
2400TH
0-25
0.120mA
A
---
9358 w/9361
1451 w/B401B
0-25
0.120mA
A
A
9358 w/9364
1451 w/B401
0-25
0.110mA
A
A
9359 w/9361
2451 w/B401B
0-25
0.120mA
A
A
9359 w/9364
2451 w/B401
0-25
0.120mA
A
A
9360 w/9361
2451TH w/B401B
0-25
0.120mA
A
A
9360 w/9364
2451TH w/B401
0-25
0.120mA
A
A
9447 w/9361
5451 w/B401B
0-25
0.120mA
A
A
9447 w/9364
5451 w/B401
0-25
0.120mA
A
A
9176
DH400I (1451DH w/DH400)
0-25
0.120mA
A
A
9177
DH400P (2451 w/DH400)
0-25
0.120mA
A
A
Notes:
1.
These detector models may be mixed and matched as long as the total maximum standby current
does not exceed 3.0 mA per initiating device circuit. The total number of detectors on a circuit
should not exceed 30.
2.
This control unit is not intended to handle more than one 2-wire detector in alarm, per circuit.
3.
The activation of a manual pull station or any other contact device, will prevent any 2-wire
detector on the same circuit from remaining activated or activating.
4.
If the smoke detector has an alarm verify function, the circuit must not be programmed for alarm
verify.
5.
When these detectors are used with 8844 or 8848 Remote LED, the standby current is doubled.
6.
For specific wiring and installation information, read the instructions provided with each device.
Содержание 12530-120
Страница 9: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I I 4 This page is intentionally blank ...
Страница 21: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I II 12 This page is intentionally blank ...
Страница 69: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I V 30 This page is intentionally blank ...
Страница 93: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I IX 12 This page is intentionally blank ...
Страница 97: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I X 4 This page is intentionally blank ...
Страница 99: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I XI 2 This page is intentionally blank ...
Страница 111: ...447138 ISSUE I REV A PAGE 2 OF 2 SAMPLE LAYOUT FOR RELAY UNITS SAMPLE LAYOUT FOR ANNUNCIATOR UNITS ...