447153 ISSUE I REV. A
PAGE 3 OF
4
413699 EVENT CODES
Event Type
SIA DCS
(8 or 20)
Ademco
Contact ID
3/1 *
1400HZ or 2300HZ
4/2 **
1400HZ or 2300HZ
Fire Alarm
FA tuvw
1 110 00 xyz
0
01
Sprinkler Alarm
SA tuvw
1 113 00 xyz
0
02
Fire Alarm Restore
FH tuvw
3 110 00 xyz
2
21
Sprinkler Alarm Restore
SH tuvw
3 113 00 xyz
2
22
Fire Supervisory
FS tuvw
1 200 00 xyz
6
64
Sprinkler Supervisory
SS tuvw
1 203 00 xyz
6
66
AC Restore
AR
3 301 00
7
70
Power Up
RR 0
1 305 00 0
7
70
Fire Unbypass
FU tuvw
3 571 00 xyz
7
71
Phone Line 1 Restore
LR 1
3 351 00 1
7
71
Phone Line 2 Restore
LR 2
3 352 00 2
7
72
Fire Trouble Restore
FJ tuvw
3 373 00 xyz
7
73
Fire Trouble Restore (all clear)
FJ 9
3 373 00 9
7
79
Fire Restore
FR tuvw
3 110 00 xyz
7
74
Sprinkler Trouble Restore
SJ tuvw
3 203 00 xyz
7
75
Sprinkler Restore
SR tuvw
3 203 00 xyz
7
76
System Battery Restore
YR
3 302 00
7
77
AC Trouble
AT
1 301 00
8
80
Fire Bypass
FB tuvw
1 571 00 xyz
8
81
Phone Line 1 Trouble
LT 1
1 351 00 1
8
81
Phone Line 2 Trouble
LT 2
1 352 00 2
8
82
Fire Trouble
FT tuvw
1 373 00 xyz
8
83
System Battery Trouble
YT
1 302 00
8
87
Fire Test Begin
FI 0
1 604 00 0
9
90
Fire Test End
FK
3 604 00
9
92
Automatic Test(unit normal)
RP N
1 602 00 N
9
93
Automatic Test (unit abnormal)
RP A
1 602 00 A
9
93
Manual Test (unit normal)
RX N
1 601 00 N
9
94
Manual Test (unit abnormal)
RX A
1 601 00 A
9
94
* The 1-digit code is programmable (3/1 codes).
** The first digit is programmable (3/1 codes)
SIA DCS
EVENT CODE IDENTIFIER DESCRIPTIONS
4 Digit Code
t
u
v
w
Sensor
0
Address (100-499)
Module
1
Address (100-499)
3 Digit Code
t
u
v
NAC Trouble
2
Circuit (01-12)
Trouble
2
9
8
GND Trouble
2
9
9
IDC
3
Circuit (01-08)
9
ADEMCO CONTACT ID
EVENT CODE IDENTIFIER DESCRIPTIONS
x
y
z
Sensor Loop 1
0
Address (00-99)
Module-Loop 1
1
Address (00-99)
NAC Trouble
2
Circuit (01-12)
Trouble
2
9
8
GND Trouble
2
9
9
IDC
3
Circuit (01-08)
Sensor-Loop 2
4
Address (00-99)
Module-Loop 2
5
Address (00-99)
Sensor-Loop 3
6
Address (00-99)
Module-Loop 3
7
Address (00-99)
Sensor-Loop 4
8
Address (00-99)
Module-Loop 4
9
Address (00-99)
Содержание 12530-120
Страница 9: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I I 4 This page is intentionally blank ...
Страница 21: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I II 12 This page is intentionally blank ...
Страница 69: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I V 30 This page is intentionally blank ...
Страница 93: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I IX 12 This page is intentionally blank ...
Страница 97: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I X 4 This page is intentionally blank ...
Страница 99: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I XI 2 This page is intentionally blank ...
Страница 111: ...447138 ISSUE I REV A PAGE 2 OF 2 SAMPLE LAYOUT FOR RELAY UNITS SAMPLE LAYOUT FOR ANNUNCIATOR UNITS ...