1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A L
P/N 447203 Issue I
II-11
RS232 Printer Output
•
Power limited
•
Not supervised
•
Voltage Range: -15 VDC to +15 VDC
•
Maximum Current (shorted): 0.050A
•
Baud Rate: 4800
•
Maximum wire loop resistance: 25 ohms
Initiating Device Circuits (Optional board P/N 12503)
•
Expandable in groups of 4 to 8 Class B, Style B circuits with optional expansion boards
Convertible to Class A, Style D circuits with optional adapter
•
Power limited
•
Supervised
•
Standby Voltage Range: 16-27 VDC
•
Maximum Standby Current: 10.3 mA
•
Maximum Smoke Detector Current: 3 mA
•
Maximum Alarm Current: 48 mA
•
Maximum Ripple: 1.5 VAC
•
Maximum Wire Loop Resistance: 100 ohms
DACT Expansion Module (Optional module P/N 12513)
•
Power limited
•
Supervised for short or open circuit
•
Maximum Voltage: 60 VDC
•
Maximum Current (shorted): 0.100 A
Alarm Relay Board (Optional board P/N 12402)
•
Power limited
•
Contact Rating:
1 A, 30VDC maximum, resistive
0.5 A, 30VAC maximum, resistive
Содержание 12530-120
Страница 9: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I I 4 This page is intentionally blank ...
Страница 21: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I II 12 This page is intentionally blank ...
Страница 69: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I V 30 This page is intentionally blank ...
Страница 93: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I IX 12 This page is intentionally blank ...
Страница 97: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I X 4 This page is intentionally blank ...
Страница 99: ...1 2 5 3 0 1 2 5 4 0 O W N E R S M A N U A L P N 447203 Issue I XI 2 This page is intentionally blank ...
Страница 111: ...447138 ISSUE I REV A PAGE 2 OF 2 SAMPLE LAYOUT FOR RELAY UNITS SAMPLE LAYOUT FOR ANNUNCIATOR UNITS ...