4.5.
50/51N/G Function. Neutral inverse time overcurrent.
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
50/51N/G
Neutral inverse time overcurrent
Permission
-
-
Yes/No
-
No
Curve
-
-
(1*)
-
Extremely Inverse
Dial
0,02
1,25
0,01
-
1,25
Tap
0,10
7,00
0,01
I nominal
0,50
Operating time
0,02
300,0
0,01
s
0,2
(1*) IEC Inverse, IEC Very inverse, IEC Extremely inverse, IEC Long time inverse, Defined time, ANSI Inverse, ANSI
Very inverse, ANSI Extremely inverse
If the option "Defined time" is selected for the curve setting, the unit behaves like an
instantaneous overcurrent unit. In this case, the unit operating time is adjusted by using the
parameter "Operating time".
If a curve (inverse, very inverse or extremely inverse) is selected for the curve setting, the
operating time depends on the curve, dial and pick-up settings.
If the unit operates as defined time, the function is activated at 100% of the set pick-up value,
and it deactivates at 95%.
If the unit operates with a curve, the function is activated at 110% of the set pick-up value, and it
deactivates at 100%. The reset is instantaneous in both cases.
The activation time is accurate to ±5% or ±30ms, whichever is higher, of the theoretical activation
time. The curves used are IEC60255-151 or ANSI-IEEEE, which are described in the "Curves"
section.
4.6.
Function CLP. Cold Load Pickup
The settings of this function are as follows:
Function
Description
Minimum
Maximum
Step
Unit
Default
CLP
Cold Load Pickup
Permission
-
-
Yes/No
-
No
Setting group
1
4
1
-
4
No Load time
0.02
300.00
0.01
s
15
Cold Load Time
0.02
300.00
0.01
s
15
The two time parameters have the following meaning:
No Load Time
: If the circuit has been open for less time than the setting, the Cold Load
Pickup function is not in working conditions.
Cold Load Time
: After the circuit has been closed, during this time the new setting group is
applied. After this time, the relay returns to the adjusted setting group.
Содержание SIA-C
Страница 1: ...Sia_Manu_Siac_Ing_R026 USER S MANUAL SIA C Dual Self powered overcurrent earth fault relay...
Страница 9: ...www fanox com Rev 26 9 188 Cut out pattern...
Страница 10: ...www fanox com Rev 26 10 188 2 2 Case Dimensions mm of SIA C with mechanics type B and C...
Страница 11: ...www fanox com Rev 26 11 188 Cut out pattern...
Страница 12: ...www fanox com Rev 26 12 188 2 3 Case Dimensions mm of SIA C with mechanics type D Cut out pattern...
Страница 13: ...www fanox com Rev 26 13 188 2 4 Case Dimensions mm of SIA C with mechanics type E and G Cut out pattern...
Страница 14: ...www fanox com Rev 26 14 188 2 5 Case Dimensions mm of SIA C with mechanics type F withdrawable Cut out pattern...
Страница 15: ...www fanox com Rev 26 15 188 2 6 KITCOM Dimensions...
Страница 16: ...www fanox com Rev 26 16 188 2 7 Striker Dimensions in mm A 44 5 B 49 5 C 56 5 D 64 5 E 42 5...
Страница 17: ...www fanox com Rev 26 17 188 2 8 TCM Dimensions...
Страница 29: ...www fanox com Rev 26 29 188 3 phase transformers Power supply and measurement solid neutral...
Страница 30: ...www fanox com Rev 26 30 188 3 phase transformers Measurement 3 phase transformer Power supply solid neutral...
Страница 31: ...www fanox com Rev 26 31 188 3 phase transformers Measurement 3 phase transformer Power supply sensible neutral...
Страница 36: ...www fanox com Rev 26 36 188 Mechanic G Three phase transformers Power supply and measurement Solid neutral...
Страница 38: ...www fanox com Rev 26 38 188 2 10 Terminals 2 10 1 Physical layout of SIA C type A and D terminals...
Страница 42: ...www fanox com Rev 26 42 188 2 10 2 Physical layout of SIA C types B and C terminals...
Страница 46: ...www fanox com Rev 26 46 188 2 10 3 Physical layout of SIA C type E terminals...
Страница 74: ...www fanox com Rev 26 74 188...
Страница 75: ...www fanox com Rev 26 75 188...
Страница 76: ...www fanox com Rev 26 76 188...
Страница 77: ...www fanox com Rev 26 77 188...
Страница 79: ...www fanox com Rev 26 79 188...
Страница 80: ...www fanox com Rev 26 80 188...
Страница 81: ...www fanox com Rev 26 81 188...
Страница 126: ...www fanox com Rev 26 126 188 Connection diagram for a RS485 bus...
Страница 186: ...www fanox com Rev 26 186 188 10 8 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 187: ...www fanox com Rev 26 187 188 NOTES...
Страница 188: ...www fanox com Rev 26 188 188...