www.fanox.com
Rev.26
125/188
7.
COMMUNICATION AND HMI
7.1.
Communication
The SIA-C relay can communicate with a local computer through its front RS232 port, or
through a remote SCADA system through the rear RS485 port. The rear RS485 port is optional
and must be specified on the list of models.
7.2.
Front communication. RS232
The RS232 communications port is installed on the front of the equipment. The connector that
is used is a DB-9 female
– DCE. The protocol that is used is Modbus RTU (19200 -8bit – no
parity
– 1 stop bit). The protocol map and documentation that are used are attached in an
appendix to this manual.
The adapter (KITCOM) can be connected to this communications port to supply the equipment
with an external battery. It should be pointed out that this port can be used simultaneously for
communication, even when the equipment is being powered by an external battery.
The PC earth should be connected to the same earth as the relay to avoid communication
problems.
7.3.
Rear communication. RS485
An option exists to fit the SIA-C with a rear communications port RS485, which must be
specified when the model is selected.
The RS485 port output has three terminals (+,- and GND), located on the rear of the
equipment. The protocol that is used is Modbus RTU (19200 -8bit
– no parity – 1 stop bit).
The protocol map and documentation that are used are attached in an appendix to this manual.
This port can be used to continuously monitor the equipment from a remote PC or SCADA
system. Up to 32 pieces of equipment can be connected to one bus; each piece with a different
Modbus address. The equipment Modbus address can be configured using the SIcom program.
To minimise communication errors as a result of noise, the use of a stranded and shielded
cable is recommended for the physical connection. All of the + terminals on one side, and all of
the - terminals on the other must be connected together in order to make the connection.
If a 3 strand cable is used for communication, the GND terminals must be connected to the
earth cable.
If a 2 strand cable is used for communication, the GND terminals must be connected to the
shielding. The shielding must be connected to the GND at only one point to avoid circular
currents.
Resistors should be used at each end if very long cables are used. The best solution for
avoiding reflection is to install resistors at both ends of the cable. The ohm value of these
resistors must be equal to the cable impedance value.
Fibre optics can be used in very aggressive environments, and they are connected by using the
corresponding converters.
If the relay is self-powered it is necessary a minimum current of 0.35xIn (single phase) or
0.17xIn (3-Phase) to communicate through RS485 port.
Содержание SIA-C
Страница 1: ...Sia_Manu_Siac_Ing_R026 USER S MANUAL SIA C Dual Self powered overcurrent earth fault relay...
Страница 9: ...www fanox com Rev 26 9 188 Cut out pattern...
Страница 10: ...www fanox com Rev 26 10 188 2 2 Case Dimensions mm of SIA C with mechanics type B and C...
Страница 11: ...www fanox com Rev 26 11 188 Cut out pattern...
Страница 12: ...www fanox com Rev 26 12 188 2 3 Case Dimensions mm of SIA C with mechanics type D Cut out pattern...
Страница 13: ...www fanox com Rev 26 13 188 2 4 Case Dimensions mm of SIA C with mechanics type E and G Cut out pattern...
Страница 14: ...www fanox com Rev 26 14 188 2 5 Case Dimensions mm of SIA C with mechanics type F withdrawable Cut out pattern...
Страница 15: ...www fanox com Rev 26 15 188 2 6 KITCOM Dimensions...
Страница 16: ...www fanox com Rev 26 16 188 2 7 Striker Dimensions in mm A 44 5 B 49 5 C 56 5 D 64 5 E 42 5...
Страница 17: ...www fanox com Rev 26 17 188 2 8 TCM Dimensions...
Страница 29: ...www fanox com Rev 26 29 188 3 phase transformers Power supply and measurement solid neutral...
Страница 30: ...www fanox com Rev 26 30 188 3 phase transformers Measurement 3 phase transformer Power supply solid neutral...
Страница 31: ...www fanox com Rev 26 31 188 3 phase transformers Measurement 3 phase transformer Power supply sensible neutral...
Страница 36: ...www fanox com Rev 26 36 188 Mechanic G Three phase transformers Power supply and measurement Solid neutral...
Страница 38: ...www fanox com Rev 26 38 188 2 10 Terminals 2 10 1 Physical layout of SIA C type A and D terminals...
Страница 42: ...www fanox com Rev 26 42 188 2 10 2 Physical layout of SIA C types B and C terminals...
Страница 46: ...www fanox com Rev 26 46 188 2 10 3 Physical layout of SIA C type E terminals...
Страница 74: ...www fanox com Rev 26 74 188...
Страница 75: ...www fanox com Rev 26 75 188...
Страница 76: ...www fanox com Rev 26 76 188...
Страница 77: ...www fanox com Rev 26 77 188...
Страница 79: ...www fanox com Rev 26 79 188...
Страница 80: ...www fanox com Rev 26 80 188...
Страница 81: ...www fanox com Rev 26 81 188...
Страница 126: ...www fanox com Rev 26 126 188 Connection diagram for a RS485 bus...
Страница 186: ...www fanox com Rev 26 186 188 10 8 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 187: ...www fanox com Rev 26 187 188 NOTES...
Страница 188: ...www fanox com Rev 26 188 188...