www.fanox.com
Installation_Guide_SIAB110FC032AC_Rev. 02
29 / 36
8. COMMISSIONING
8.1. Thermal resistance
The relay can support, with 3-phase balanced injection, the following values according to
International Standards:
•
4 x In continuously.
•
20 x In for 10 seconds.
•
100 x In for 1 second.
In the following table the different injection modes are described:
CURRENT
GENERATION
INJECTION
MODE
INJECTION
SYSTEM
RELAY
REAR
CONNECTION
RELAY
WITHSTAND
ENERGY WAVEFORM
Single phase
Phase-
Neutral
NOT APPLY
P-N:
Phase-
Phase
P-P:
Three phase
Phase-
Neutral
Balanced (120°)
Unbalanced (0°)
P-N Balanced:
P-N Unbalanced:
= 2x