Output 2 is activated
-
Led 1 is activated
-
Led 3 is activated
TEST 2
Settings:
-
Permission: YES.
-
Curve: IEC Inverse.
-
Dial: 1
-
TAP: 0.5xIn.
-
Theoretical tripping time = 4.98 seconds
(Fault current 2 A)
The following information will be checked:
-
Trip output is activated
-
Output 2 is activated
-
Led 1 is activated
-
Led 3 is activated
TEST 3
Settings:
-
Permission: YES.
-
Curve: IEC Inverse.
-
Dial: 1
-
TAP: 0.5xIn.
-
Theoretical tripping time = 2.97 seconds
(Fault current 5 A)
The following information will be checked
:
-
Trip output is activated
-
Output 2 is activated
-
Led 1 is activated
-
Led 3 is activated
•
51G Inverse time neutral overcurrent protection:
TEST 1
Settings:
-
Permission: YES.
-
Curve: IEC Inverse.
-
Dial: 0.05
-
TAP: 0.3xIn.
-
Theoretical tripping time= 3.67 seconds
(Fault current 0.33 A)