By default, the configuration is:
OUTPUT
LOGICAL GATE
BINARY STATES
PHYSICAL
OUTPUTS
Output 1
NOR4
•
Ready
Output 2
AND4
•
Phase Trip
•
General Trip
Output 3
AND4
•
Ground Trip
•
General Trip
Trip Output
OR4_PULSES
•
General Trip
LOGIC
52a
Not configured
----
52b
Not configured
----
External trip
OR4
•
Input 1
Block 50
Not configured
----
Block 50G
Not configured
----
Settings group 1
OR4
----
Settings group 2
Not configured
----
Reset
OR4
•
Input 3
Logic Signal 1
Not configured
----
Logic Signal 2
Not configured
----
Logic Signal 3
Not configured
----
Logic Signal 4
Not configured
----
Outputs require, to be activated, the following mínimum current:
To get the outputs all together to be operative at the same time, it is required Single
phase
→
305 mA or Three phases
→
170 mA. To activate an output it is required Single
phase
→
270 mA or Three phases
→
90 mA. Once the relay detects these levels of current these
outputs are instantaneously operative.