4. TECHNICAL SPECIFICATIONS
Complete model
SIAB110FC232AC:
1: Phase Measurement
→
In=1 A; (0.10-30.00 A)
1: Neutral Measurement
→
In=1 A; (0.05-16.00 A)
0: Net Frequency
→
Defined by General Settings
F: Power Supply
→
Self-p 24-230 Vdc / Vac (Dual) + Commissioning Battery
C: Additional Functions
→
+ 49 + SHB + 4 Settings LDP + DFR + 52
2: Communications
→
USB (Modbus RTU) + RS485 (Modbus RTU or DNP3.0)
3: Inputs and Outputs
→
4 LEDs + Trip (striker) + 3 O 3 Inputs
2: Mechanics
→
Extended Horizontal Assembly
A: Languages
→
English, Spanish and German
C: Adaptation
→
Standard CTs /1
Function
50_1
Function Enable: Yes/No/SHB
Current Tap: 0.10 to 20 xIn (step 0.01 xIn)
Time Delay: 0.02 to 300 s (step 0.01 s)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Timing accuracy:
Without SHB permitted: ± 30 ms or ± 0.5% (greater of both).
With SHB permitted: ± 50 ms or ± 0.5% (greater of both).
Function
50G_1
Function Enable: Yes/No/SHB
Current Tap: 0.10 to 10 xIn (step 0.01 xIn)
Time Delay: 0.02 to 300 s (step 0.01s)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Timing accuracy:
Without SHB permitted: ± 30 ms or ± 0.5% (greater of both).
With SHB permitted: ± 50 ms or ± 0.5% (greater of both).
Function
50/51
Function Enable: Yes/No/SHB
Current Tap: 0.10 to 7 xIn (step 0.01 xIn)
Curves: IEC 60255-151 and IEEE
Curve Type: IEC Inverse curve, IEC very inverse curve, IEC extremely inverse curve IEC long time
inverse, IEEE Inverse curve, IEEE very inverse curve, IEEE extremely inverse curve, Defined Time.
Time Delay: 0.02 to 300.00 s (step 0.01 s)
Time Dial (TMS): 0.01 to 1.5 (step 0.01)
Curve, activation level 110%
Curve, deactivation level 100%
Defined time, activation level 100%
Defined time, deactivation level 95%