1. Disconnect the power supply.

2. Mount the indicator on the rail in the distribution box.

3. Connect the neutral wire to terminal N.

4. Connect the input phase to terminal 1.

5. Connect the measured circuit or single receiver to terminal 3 

(output phase L) and to N.

6. Connect terminals 23, 24 and 25 to the RS-485 network.

Program for test reading of the counted energy value and for 

basic settings of the meter parameters. 

Available at www.fif.com.pl (on the device’s subpage). 

For communication of the meter with the computer, the USB 

converter CN-USB-485 or any RS-485/USB standard is required.

installation 2-wire

rated voltage 

230 V AC

minimum measured current 

0.02 A

base current 

5 A

maximum current 

100 A

voltage measuring range 

100÷289 V AC

measurement accuracy (EN50470-1/3) 

class B

rated frequency 

50 Hz

insulation protection class 

II

housing 

PC material

own power consumption 

8 VA; 0,4 W

indication range 

0÷99999 kWh

constant 

1000 pulses/kWh

Mounting

LE Config service programm

Technical data

Содержание LE-01MR

Страница 1: ... pulses kWh In addition the meter measures the pa rameters of the supply network and the temperature of its own system The values are indicated cyclically on the LCD display Compliance Purpose Functioning F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Donotdisposeofthisdeviceinthetrashalongwithother...

Страница 2: ...ordance with the Modbus RTU standard via the RS 485 serial port The read out values of registers after conversion give results according to the indica tions on the indicator display Active energy consumed AE AE kWh Reactive energy AE kWh Phase voltage U V Phase current I A Frequency F Hz Active power P W Reactive power Q var Apparent power S VA Power factor cosϕ Description of measurement and conf...

Страница 3: ...he meter register The default meter address 1 The meter is marked with individual serial number allowing its unambiguous identification The marking is laser engraved and cannot be removed The meter has sealable input and output terminal covers to pre vent any attempts to bypass the meter Meter address Meter number Sealing ...

Страница 4: ... 4 Front panel ...

Страница 5: ... 5 1 LIN power input 3 LOUT power output N N wire neutral 23 RS 485 output A 24 RS 485 output GND 25 RS 485 output B Wiring diagram ...

Страница 6: ...f the meter parameters Available at www fif com pl on the device s subpage For communication of the meter with the computer the USB converter CN USB 485 or any RS 485 USB standard is required installation 2 wire rated voltage 230 V AC minimum measured current 0 02 A base current 5 A maximum current 100 A voltage measuring range 100 289 V AC measurement accuracy EN50470 1 3 class B rated frequency ...

Страница 7: ...800 9600 bps parity NONE ODD EVEN stop bits 1 read out signalling red LED working temperature 25 55 C terminal 100 A 25 mm screw terminals RS 485 1 mm screw terminals tightening torque 0 4 Nm dimensions 1 module 18 mm mounting on TH 35 rail ingress protection IP20 _________________ factory settings ...

Страница 8: ...es that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE and MID Declaration of Conformity along with the refe rences to the standards in relation to which conformity is decla red can be found www fif com pl on the product subpage Dimensions Warranty CE declaration E210529 ...

Отзывы: