background image

- 8 -

The changeover contact of the relay allows to connect 

a visual or audible signalling system that informs abo-

ut the relay activation, which means switching off the 

motor.

power supply 

3×400 V

contact 

separated 2×NO/NC

maximum load current  (AC-1) 

2×6 A

power supply control  

2×LED

minimum phase voltage  

320 V

maximum phase voltage  

480 V

voltage asymmetry of activation 

20÷80 V

voltage hysteresis 

5 V

switch-off delay on asymmetry 

1÷10 sec

switch-off delay in case of phase failure 

1 sec

switch-on delay 

1÷60 sec

power consumption 

1.6 W

working temperature 

-25÷40°C

Contacts configuration

Technical data

Содержание CKF-318 TRMS

Страница 1: ...true rms value of the voltage TrueRMS even when the power supply voltage is disturbed distorted Purpose F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48...

Страница 2: ...ental shutdowns in case of temporary interferences in the power supply network If the voltage drops below 320 V or rises above 480 V the discon nection is carried out after 1 sec The countdown to shut...

Страница 3: ...3 Front panel...

Страница 4: ...current state of the output Asymmetry or exceeding of the voltage threshold Relay switched off voltage value of any of the phases below 150 V or above 280 V or asymmetry above the set value Incorrect...

Страница 5: ...5 Voltage waveforms Legend T1 1 10 sec T2 1 60 sec...

Страница 6: ...erminals of the device the relay will be switched off immediately The red LED will be on to indicate a phase sequence error When the correct phase sequence returns the relay will be switched on with a...

Страница 7: ...1 Swap the 2 phases for example L2 with L3 12 Switch on the power supply the motor can be started 13 In any other case than those described in points 8 and 9 see the signaling table page 4 Wiring diag...

Страница 8: ...t separated 2 NO NC maximum load current AC 1 2 6 A power supply control 2 LED minimum phase voltage 320 V maximum phase voltage 480 V voltage asymmetry of activation 20 80 V voltage hysteresis 5 V sw...

Страница 9: ...nly with proof of purchase Contact your dealer or directly with us F F Filipowski sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 3...

Страница 10: ...ltage circuit breakers Before connecting the power supply make sure that all cables are connected correctly It is essential to observe the operating conditions of the sensor supply voltage humidity te...

Страница 11: ......