Gnd
7
g
E
Energy saving mechanical ventilation.
•
No possibility to switch to natural ventilation.
•
iFan connection to extra Analog output of PWM2A
board.
•
Use the control 10-0Volt at Lumina 17, Lumina 21,
Lumina 37, Lumina 38
•
No DSR readout or calibration on the controller with
10-0V. When control is 10-0V, calibration only possible
on ITM-iF itself by dipswitch 9 and 10 (see manual).
•
When ITM-iF controlled by Lumina 37 or Lumina 38 on
I/O-Net then there is no read out of the DSR feedback
on those controllers. Only possible with ITM-iF control
by I/O net with Lumina 21 or Lumina 17. (PROFLOW
ENDSTATION)
•
ITM-iF control by I/O-Net on Lumina 21 or Lumina 17,
calibration is possible on the Lumina 21 of Lumina 17.
This is not possible by Lumina 37 or Lumina 38
F
Energy saving mechanical ventilation and natural vent.
(PROFLOW ENDSTATION)
•
The same as energy saving mechanical ventilation with
the possibility to switch over to natural ventilation.
G
Traditional mechanical ventilation (PROFLOW
ENDSTATION)
•
The same as energy saving mechanical ventilation with
no possibility to switch over to natural ventilation.
•
In this mode the iFan will control on a higher speed.
H
Mechanical with several units (PROFLOW
ENDSTATION)
•
The same as energy saving mechanical ventilation with
no possibility to switch over to natural ventilation.
•
Use this mode when more iFans with ATM units
connected parallel in one house, for example ridge
ventilation in a poultry house.