Aura 37
Alarm
14
Alarm messages
Temperature alarms
Alarm
Action
Min.house temp. (abs)
Max.house temp. (abs)
Min.house temp. (dif)
Max.house temp. (dif)
Minimum alarm
Check wiring and sensors.
Check if the heater works properly (if available).
Check minimum difference alarm settings.
Maximum alarm
Check wiring and sensors.
Check if the cooling works correctly (if available).
Check maximum difference alarm settings.
Check absolute maximum alarm settings.
System alarms
Alarm
Action
Backup alarm
The control computer will be active on factory settings. Please check the
settings.
Watchdog alarm
Communication alarm
Setting changed
Stack overflow
Communication assignment
EPROM error
System error
Protected software
The control computer also tests a number of functions of the
control computer itself. Always warn the installer if a system
alarm occurs.
Power failure
When the control is powered up, a silent alarm will be given.
Sensor failure
Sensor measurement is reliable between -9.9 and +99.9. The control
computer will give an alarm when the sensor goes out of range. The
control computer will continue controlling based on another sensor if
connected.