2.0 SSG UPS CIRCUIT DESCRIPTIONS

Input Filter

This portion of the circuit provides surge protection, certified to meet IEC 61000-4-5 and IEC 801-5.
It also filters out both electro-magnetic interference (EMI) and radio frequency interference (RFI) and
prevents excessive levels from being conducted back to the utility source. All SSG Series rackmount
models have been tested and comply with FCC Class B requirements. 

Input Power Factor Correction

While the UPS is operating from the utility source, this circuit converts utility AC power to regulated
DC power for inverter use. It corrects the input current to maintain a sine waveform to minimize the
amount of current distortion that will be reflected back to the utility.  

DC/DC Converter

The DC/DC converter utilizes energy from batteries and boosts up the DC bus voltage to a level
required by the inverter.  This allows the inverter to operate continuously at optimum efficiency and
voltage. The converter incorporates a patented circuit which reduces the amount of ripple current
and EMI interference to the battery, increasing the overall battery life.

DC/AC Inverter

In utility mode operation, the inverter utilizes the regulated DC output to invert DC back into clean,
regulated sinewave AC power.  When utility power fails, the inverter will receive its energy from the
battery through the DC/DC converter. In both modes of operation, the UPS inverter is on-line and
continuously generating clean, regulated AC output power to the load. The IGBT, PWM inverter is of
a very robust design and produces a pure sinewave output with a +/-2% voltage regulation. Having a
very low output impedance, it can supply the high current demands of high inrush and non-linear
loads. 

Battery Packs

The SSG Series UPS utilizes a flame retardant battery pack comprised of four 12V, 7AH, 
valve-regulated, sealed lead acid (VRLA) batteries in each pack. All SSG battery packs are 
interchangeable between SSG 1.5kVA-3kVA models. They are easily replaced through the UPS front
panel. See replacement instructions outlined in this manual.

To maintain the optimum battery life, the user should operate the UPS in an ambient temperature of
68ºF to 77ºF (20ºC to 25ºC). Some SSG Series UPS models have batteries that may be rated oper-
ational at -20º C - 55º C (-4º F to 131º F), at these temperatures, battery life will be substantially
reduced. Optional extended battery modules are available through Falcon and will extend the
amount of battery runtime. Please refer to the exact UPS model in the attached specificaitons for the
specific battery option part number.  

Battery Charger

The battery charger utilizes energy from the utility power to continuously charge the UPS batteries.
The charger operates in "constant power" mode. The UPS batteries are being charged whenever the
UPS is plugged in, turned on and operating from utility power. The internal UPS battery charger 
output is rated at 1 amp.

CAUTION: When making battery bank connections to the UPS, alwasy verify the battery bank
circuit breaker(s) are in the off position. PRIOR to turning on the first battery bank circuit
breaker, ALWAYS DEPRESS AND HOLD THE BATTERY PRECHARGE PUSHBUTTON LOCATED
ON THE UPS REAR PANEL WHILE TURNING ON THE FIRST BATTERY BANK CIRCUIT 
BREAKER TO PREVENT UPS DAMAGE.

6

Содержание SSG1.5KRM-1

Страница 1: ...n SSG3KRM 1 3kVA 2100W 120Vac 20 C 55 C 4 F to 131 F Operation SSG3KRM HW 3kVA 2100W 120Vac 20 C 40 C 4 F to 104 F Operation SSG3KRM 2 3kVA 2100W 230Vac 20 C 55 C 4 F to 131 F Operation FALCON Electri...

Страница 2: ...s LCD LED indicators icons 16 Function Test button 17 Set Alarm Silence button 17 How to display the UPS Parameters 17 Chapter 5 UPS Operation Operating Modes 18 Normal On line Mode 18 Battery Mode 18...

Страница 3: ...nt Control Remote Emergency Power Off REPO Input Power Factor Correction Wide Input Voltage Window Precision Output Voltage Regulation Superior Brownout Surge and Transient Protection Optional Frequen...

Страница 4: ...S in an indoor environment with an ambient temperature range specified by model number herein This UPS is designed for use with industrial scientific or data processing class equipment DO NOT USE TO P...

Страница 5: ...Function Test and Set Alarm Silence buttons Two levels of audible alarms are also provided when the unit is operating on battery The SSG Series rear panel supports the following a Load Segment Contro...

Страница 6: ...t design and produces a pure sinewave output with a 2 voltage regulation Having a very low output impedance it can supply the high current demands of high inrush and non linear loads Battery Packs The...

Страница 7: ...d design in relation to the packaging s capacity and its intended use SAVE THE ORIGINAL SHIPPING CARTON INSERTS AND PACKING MATERIALS 6 Each consignment with packages bearing the lithium battery handl...

Страница 8: ...Across The Batteries as Personnel Injury Fire or Explosion May Result 8 DANGER NEVER ATTEMPT TO CONNECT AN EXTENDED BATTERY BANK CONTAINING VRLA LEAD ACID BATTERIES TO A UPS CONTAINING INTERNAL LITHI...

Страница 9: ...ing The SSG Series UPS may be shipped in a number of boxes depending on the model and configuration ordered The number of boxes you have received should be as indicated MODEL BATTERY MODULE NUMBER OF...

Страница 10: ...er or into a 19 inch equipment rack Follow the appropriate instructions in either Rackmount UPS Setup or Free standing UPS Installation Rackmount UPS Setup All SSG Series models are shipped with front...

Страница 11: ...istance needed 6 Attach the two mounting brackets to the rack s mounting rails The brackets allow adjustment of up to eight inches of the slide assembly mounting position front to back on the rack mou...

Страница 12: ...e UPS into a dedicated wall receptacle that is protected by a circuit breaker or fuse in accordance with national and local electrical codes Use a 15 amp rated device for 1500 VA units 20 amp for the...

Страница 13: ...ew the LCD board and rotate it 90 degrees to the correct position for viewing Use care when handling the LCD display and associated cabling Mount the front covers back and reinstall the screws SSG HW...

Страница 14: ...5 8 217 5 243 13 184 6 8 261 7 150 283 5 15 221 7 8 304 5 SSG2 2KRM 1 HW SSG2 2KRM 2 HW SSGR 1 12 40 5 96Vdc 2 24 SSGR 1 SSGR 2 1 7 1 120Vac 3A 2 230Vac 1 5A 109Vdc 2 x 54Vdc 2A 2 Chargers 1A each 43...

Страница 15: ...the unit and to prevent them from tipping over One additional set of mounting feet base extensions ships with each battery bank 3 Turn off the battery disconnect switch and connect the supplied batter...

Страница 16: ...tery mode this icon will be displayed Battery Level The battery icon or LED indicates the battery capacity The more battery capacity available the more bars that will be illuminated Each bar represent...

Страница 17: ...onds During that period the battery if first determined to be good will supply power to the UPS Should defective batteries be detected the audible alarm will sound one long tone and the UPS will conti...

Страница 18: ...t to the charger and into the battery BATTERY MODE OPERATION The battery mode icon configuration is displayed during a loss of utility power or during excessively high line voltage conditions When in...

Страница 19: ...flashing If the load is increased to over 3 of the UPS output rating the UPS will automatically switch back to normal on line operation All SSG models are shipped from the factory with Green Mode tur...

Страница 20: ...status BIT 7 has a Dot or No Dot displayed for the function bit selected To select a dot or no dot for the function you are presently in press the Set Alarm Silence button to turn on Dot or turn off...

Страница 21: ...st buttons at same time again and hold for one second The alarm buzzer will sound one short beep to acknowledge the UPS has stored the setting How to Set the UPS Output Voltage Function Bits 0 1 The S...

Страница 22: ...ge the UPS has stored the settings 7 You must now restart the UPS before the new voltage setting will be in effect How to Set the UPS Load Segment Control Options Function Bits 3 4 5 6 Three condition...

Страница 23: ...peatedly and move the dot to function BIT 4 for load segment 1 or BIT 6 for load segment 2 3 Press the Set Alarm Silence button once to turn on dot Status BIT 7 4 Press the Set Alarm Silence and Funct...

Страница 24: ...into the Advanced Communications Option Slot the RS 232 port and UPSilon software may not be used The USB port may be used in conjunction with UPSilon software concurrently with the SNMP HTTP agent RS...

Страница 25: ...PO connection is not used The REPO function provides an interface for a NFPA 70 NEC 645 11 compliant Remote Emergency Power Off REPO switch The switch must have a normally closed contact state that op...

Страница 26: ...ote J1 J7 must be all configured 1 2 or 2 3 or UPS and PC may be damaged J9 Summery Alarm 1 2 Normally Closed Default 2 3 Normally Open J10 Low Battery 1 2 Normally Closed 2 3 Normally Open Default J1...

Страница 27: ...SSG2 2KRM HW SSG3KRM HW Rear Panel Layout OUTPUT WIRING DETAILS 27 LS1 Neutral LS1 Line LS2 Neutral LS2 Line GND...

Страница 28: ...place Batteries We suggest the battery pack s containing 10 12 year batteries have the batteries replaced every 8 10 years for SSG units that are operated and maintained in a 25 C environment Higher t...

Страница 29: ...pack Take care not to destroy the packaging Compare new and old battery packs and verify that they are the same type If so proceed with the next step otherwise stop and contact Falcon Service 6 Line...

Страница 30: ...on Service 7 Line up and slide in the new replacement battery packs with right polarity by verifying against the marked battery pack 8 Reinstall the battery stop plates with the screws previously remo...

Страница 31: ...nnectors are provided on each battery module to allow for a daisy chain connection to all modules and the UPS Performing a Manual Battery Test Pressing the Function Test button for three seconds while...

Страница 32: ...name and address of the nearest battery recycling facility NEVER open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic A battery can present a...

Страница 33: ...TING Audible Alarms The SSG Series UPS features audible alarm codes to alert the user of potential problems Please refer to the following table to identify and resolve alarms and the conditions causin...

Страница 34: ...1 Bit 2 Bit 3 Bit 6 and Bit 7 errors the UPS must be immediately turned off and the Falcon service department contacted Attempting to turn the UPS back on may result in furter damage to its internal e...

Страница 35: ...empting any troubleshooting always verify the UPS battery fuse is installed and the input voltage input plug and wiring are correct Please refer to the table below and attempt to solve the problem pri...

Страница 36: ...nce to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television recepti...

Страница 37: ...use the original shipping container and packing materials will likely result in the unit being received by Falcon with shipping damage Falcon Electric will not assume any responsibility for shipping d...

Страница 38: ...de of Falcon s control such as fire accidents impacts iv normal wear and tear such as cleaning and replacement of batteries The warranty is null and void if i the product is used in conjunction with l...

Страница 39: ...es N A N A 6 minutes 18 minutes N A N A Recharge Time 8 Hours to 90 Transfer Time Line Fails Recovers Zero UPS to Bypass or Reverse 4ms After Overload Auto Transfer to UPS With Frequency Converter Opt...

Страница 40: ...VRLA Batteries 12Vdc 7AH Number of Battery Packs 48Vdc 2 Recharge Time 8 Hours to 90 Transfer Time Line Fails Recovers Zero UPS to Bypass or Reverse 4ms After Overload Auto Transfer to UPS With Frequ...

Отзывы: