SSG-HW Series
TM
Industrial-Grade UPS PLUS
®
2.2kVA - 3kVA
Model Number
SSG2.2RM-1-HW
SSG2.2RM-2-HW
SSG3KRM-1-HW
SSG3KRM-2-HW
Nominal VA
2200
3000
Electrical Input
Nominal AC Voltage
-1 Models =120Vac
-2 Models = 208-240Vac
AC Voltage Range
-1 Models = 80-138Vac
-2 Models = 160-276Vac
Frequency
50/60 Hz ± 5% (Auto Tracking)
Power Factor Correction
> 0.97
Surge Suppression
IEEE/ANSI C62.41
Efficiency (Typical)
> 87%
Electrical Output
Watts
1540
2100
AC Voltage (User Programmable)
-1 Models = 100, 110, 115 or 120Vac (sinewave)
-2 Models = 208, 220, 230, 240Vac (Sinewave)
Frequency
50/60 Hz (Auto Tracking or user programmable fixed 50 or 60Hz modes)
Frequency Stability
± 0.3% (Battery Mode), ±5% Synchronized to the input frequency in utility mode
Voltage Regulation
Voltage Regulation
Step Load Change
± 7% for 100% load variation, recovery in 5ms
Harmonic Distortion
< 3% Linear Load, < 5% Non-Linear Load
Overload
150% for 10 seconds, 110% for 20 seconds, 105% for 50 seconds
Crest Ratio
3:1
Battery
DC Bus Voltage
96Vdc
Back Up Time
@Full Load
@1/2 Load
8 minutes
20 minutes
6 minutes
18 minutes
Battery Pack Type
User-Replaceable, Hot-Swappable individual 48Vdc packs
Battery packs are replaceable through the front panel without removing the UPS, battery bank or EBM from the rack
Long-life, 8 to 10 Year, Maintenance-Free, Sealed VRLA Batteries, 12Vdc, 7AH
Number of Battery Packs (48Vdc)
(2)
Recharge Time
8 Hours to 90%
Transfer Time
Line Fails/Recovers
Zero
UPS to Bypass or Reverse
< 4ms
After Overload
Auto Transfer to UPS
With Frequency Converter Options
Bypass Disabled
Electrical Connections
Input
-1 Models = 6’ line cord with 5-20P
-2 Models = 6’ line cord with Schuko
The plug may be removed and cord used to hardwire
-1 Models = 6’ line cord with L5-30P
-2 Models = 6’ line cord with Schuko
The plug may be removed and cord used to hardwire
Output
Hardwire Terminal Block
Environmental
Temperature
Operational
Storage
-20ºC to +40º C (-4ºF to 104ºF)
-15ºC to +50ºC (5ºF to 122ºF)
Humidity
10% to 95% Non – Condensing
Altitude
10,000 Feet (3000 meters) without derating
Cooling
Low Velocity Forced Air Fans
Heat Dissipation (BTU/Hour)
784
1071
Audible Noise
@ 1 Meter
<50dBA
Controls & Indicators
LCD Display
MIMIC Graphical Display, Input/Output Voltage, Frequency & Load, Alarm, Programmable settings & UPS state icons
Audible Alarms
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm
Load Segment Control
Two programmable load segments, one continuous load segment
Remote Emergency Power Off (or)
Remote Output Receptacle Control
(Standard) Meets NFPA 70, NEC 645-11 (REPO connections located on the UPS rear panel)
(Optional) UPS Load Segment Controlled Output Receptacles can be turned off and on using a remote isolated switch contact.
Communications
USB Port, RS-232C Serial Port, Optional SNMP/HTTP Agent Board (UPS Bundled UPSilon Software)
Mechanical
Dimensions UPS inches (mm)
H x W x D
Standard Battery Module
(2U) 3.5 x 16.8 x 21.3 (88.5 x 426 x 540)
(2U) 3.5 x 16.8 x 21.3 (88.5 x 426 x 540)
(2U) 3.5 x 16.8 x 21.3 (88.5 x 426 x 540)
Weight lb. (kg) UPS
Battery Bank
32 (14.5)
70.6 (32.1)
Agency Listing
-1 Models UL 1778, CUL, FCC Class B, -2 Models CE,UL 1778, CUL