Example - How to Set the UPS Output Voltage to 115Vac (-1 models) or 230Vac (-2 Models)
1. Press the "Function/Test" and "Set/Alarm Silence" buttons at same time and hold
them for one second. The unit will emit one alarm beep and then enter the
Configuration Mode.
2. Press the "Function/Test" button eight times to move the dot to function BIT 0.
3. Press the "Set/Alarm Silence" button turn off (no dot) Status BIT 7.
4. Press the "Function/Test" button one time and move the dot to function BIT 1.
5. Press the "Set/Alarm Silence" button to turn on (dot) Status BIT 7.
6. Press the "Set/Alarm Silence" and "Function/Test" buttons at same time again
and hold for one second. The alarm buzzer will sound one short beep to acknowledge the
UPS has stored the settings.
7.
You must now restart the UPS before the new voltage setting will be in effect.
How to Set the UPS Load Segment Control Options (Function Bits 3, 4, 5 & 6)
Three conditions of automatic load segment control may be programmed for two separate output
load segments. Additionally, one continuous load segment is provided. Per the model-specific rear
panel pictures that follow, the two programmable and one continuous load segments are assigned to
specific output receptacles located on the UPS rear panel.
For each programmable load segment, the following conditional states may be selected:
1. Turn off the assigned load segment when utility power is lost (bits 3 & 5)
2. Turn off the assigned load segment whenever low battery is reached (bits 4 & 6).
3. Load segment bits are turned off making the load segment continuous.