18
4.3.1.3 Shutdown
1. Shutdown in AC Mode
Press and hold the OFF button
for 5 seconds until the buzzer beeps. The
UPS will cut the power supply to the outlets. The ventilating fans will continue to
operate. Switch off the AC power source. The ventilating fans will stop. The UPS is
now completely shut down.
2. Shutdown in DC Mode
Press and hold the OFF button
for 5 seconds until the buzzer beeps.
The UPS will cut the power supply to the outlets. The LEDs will turn off, and the
ventilating fans will stop after 10 seconds. The UPS is now completely shut down.
4.3.1.4 Battery Self-test in AC Mode
After the UPS has been successfully started in AC mode, press and hold the
Self-Test button
for 5 seconds until the buzzer beeps. The
LED will
illuminate to indicate that the self-test is in progress. When the self-test is
completed the UPS will return to AC mode. If there were no faults or abnormal
conditions then the LED indicators
and
LEDs will turn off.
Note: The main function of battery self-test is to run a discharge test on
the batteries to check condition.