background image

If it is found that there is excessive draught in the
chimney then a draught stabiliser should be fitted.
Fitting of a draught stabiliser will affect the require-
ment for the permanent air supply into the room. 

Adequate provision e.g. easily accessible soot door
or doors must be provided for sweeping the chimney
and connecting fluepipe.

ALL FLUE INSTALLATIONS ARE THE 
RESPONSIBILITY OF THE CUSTOMER.

INSTALLATION CLEARANCES

Maintain at least the following clearances to all 
combustible material:

VENTILATION & COMBUSTION AIR 
REQUIREMENTS

It is imperative that there is sufficient air supply to
the stove in order to support correct combustion.
The air supply to this appliance must comply with
current Building Regulations.  If another air using
appliance is fitted in an adjacent room it will be nec-
essary to calculate an additional air supply.

All materials used in the manufacture of air vents
should be such that the vent is dimensionally stable,
corrosion resistant, and no provision for closure.
The effective free area of any vent should be ascer-
tained before installation. The effect of any grills
should be allowed for when determining the effective
free area of any vent.

Air vents direct to the outside of the building should
be located so that any air current produced will not
pass through normally occupied areas of the room.

An air vent outside the building should not be  locat-
ed less than the dimensions specified within the
Building Regulations from any part of any flue termi-
nal. These air vents must also be satisfactorily fire
proofed as per Building Regulations.

Air vents in internal walls should not communicate
with bedrooms, bedsits, toilets, bathrooms or rooms
containing a shower.

Air vents traversing cavity walls should include a
continuous duct across the cavity. The duct should
be installed in such a manner as not to impair the
weather resistance of the cavity.

Joints between air vents and outside walls should be
sealed to prevent the ingress of moisture. Existing
air vents should be of the correct size and unob-
structed for the appliance in use. If there are fans or
other air using appliances installed in adjacent
rooms in the dwelling where the stove is installed,
additional air vents must be installed to deliver 
adequate air supply to all air using appliances 
operating at full output or max settings. 

Where such an installation exists, a test for spillage
should be made with the fan or fans and other appli-
ances using air in operation at full rate, (i.e.extrac-
tion fans, tumble dryers) with all external doors and
windows closed. 

If spillage occurs following the above operation, an
additional air vent of sufficient size to prevent this
occurrence must be installed.

PERMANENT AIR VENT

The stove requires a permanent and adequate air
supply in order for it to operate safely and efficiently.
In accordance with current Building Regulations the
installer will have fitted a permanent air supply vent
into the room in which the stove is installed to pro-
vide combustion air.  This air vent should not under
any circumstances be shut off or sealed.

Extractor Fan

There must not be an extractor fan fitted in the same
room as the stove as this can cause the stove to
emit smoke and fumes into the room.

7

From the Front

910mm 

From the Back

750mm

From the Sides

750mm 

From the Flue Pipe (Vertical no
heat shield fitted)

750mm 

Mantle Clearance

700mm 

Side Trim Clearance

750mm 

Brick wall minimum clearance, but allow access
for controls, servicing & side load door. 

Содержание Reginald

Страница 1: ...Children aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the...

Страница 2: ...on 9 13 Floor Protection 9 14 Flue Locations 9 15 Handover 9 16 Technical Data 10 17 Specification 10 18 Installation Check list 11 19 Operating Instructions 12 20 Important Notes 12 21 Side Load Door...

Страница 3: ...tove care should be taken to avoid the possibility of personal injury IMPORTANT WARNING This stove must not be installed into a chimney that serves any other heating appliance 2 The complete installat...

Страница 4: ...ean the chimney such as a soot box access door in the flue for cleaning See Fig 3 for recommended locations For top flue outlet see Fig 4 place the top flue con nector on the flue outlet use fire ceme...

Страница 5: ...l into the room If this occurs shut the appliance down by closing the air controls If the problem persists seek the advice of a chimney sweep When installing a chimney care must be taken to ensure the...

Страница 6: ...ng through the walls of fireplaces or flues could ignite it Therefore when installing the stove in the presence of combustible materials due account must be taken of the guidance on the sepa ration of...

Страница 7: ...Fig 9 Fig 10 Fig 11 Fig 12 Fig 13 Fig 14 6 CLEARANCE TO COMBUSTIBLES CORNER INSTALLATION ALCOVE INSTALLATION FIREPLACE INSTALLATION FLUE CLEARANCES MINIMUM COMBUSTIBLE ALCOVE MANTLE CLEARANCE...

Страница 8: ...ms bedsits toilets bathrooms or rooms containing a shower Air vents traversing cavity walls should include a continuous duct across the cavity The duct should be installed in such a manner as not to i...

Страница 9: ...m opposite poles North South East West of the dwelling and tee off for the air sup ply to the stove This should negate the effect of suction and pressure zones See Fig 15 Fig 15 Note When Installing o...

Страница 10: ...quired for the controls and side load door See Fig 16 FLUE LOCATIONS Flue outlet to suit 150mm internal diameter flue pipe Fig 17 9 Fig 16 HANDOVER On completion of the installation allow a suitable p...

Страница 11: ...Flow 8 9 g s Flue Gas Temperature at Nominal Output 318oC Gross Weight 250kgs Flue Outlet 150mm Flue Draught 12 Pascals Max Log Size 480mm WARNING DO NOT OBSTRUCT PRIMARY AIR SUPPLY TO THE STOVE SPECI...

Страница 12: ...serving this appliance should not serve any other appliance 6 Access should be provided to the chimney serving the appliance to allow for cleaning Location 7 Clearance to combustible materials must be...

Страница 13: ...e has thorough ly cooled IMPORTANT NOTES 1 Do not burn fuel with a high moisture content such as unseasoned timber This will result in a build up of tar in the stove and in the chimney 2 Clean the flu...

Страница 14: ...ire down do not add fuel make sure that the firedoor is properly closed and that the primary and secondary air controls are all in the closed position Cutting off the air supply will reduce the heat o...

Страница 15: ...g may occur However persistent fume emission is potentially dangerous and must not be tolerated If fume emission does persist then the following immediate action should be taken a Open doors and windo...

Страница 16: ...by sliding it to the fornt of the stove lift it and push it to one side allowing the opposite to fall into the stove Replace in reverse order when chimney cleaning is complete See Figs 24 25 NOTE Wher...

Страница 17: ...nd that the air control is open to avoid condensation in the stove firebox and possible corrosion during this shutdown period DOOR LATCH ADJUSTMENT If the door latch should be come loose over time due...

Страница 18: ...17 EXPLODED VIEW...

Страница 19: ...Y AIR TUBE FRONT F01193AXX 27 SERIAL NUMBER PLATE N00234BXX 28 DATA PLAQUE N00619AXX 29 HEAT EXCHANGER Q00781AXX 30 GRATE Q00782AXX 31 BACK LINER Q00783AXX 32 SIDE LINER LH Q00784AXX 33 SIDE LINER RH...

Страница 20: ...Manufactured by Waterford Stanley Ltd Unit 210 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 DP 141223 N00562AXX...

Отзывы: