SECTION 3 -

 

SERVICING and CONVERSION

 

Important

 

BEFORE  ATTEMPTING  ANY  SERVICING,  ENSURE  ISOLATING  COCK  IS  TURNED  OFF  AND 

THAT  IT  CANNOT BE INADVERTENTLY TURNED BACK ON.

 

ENSURE  UNIT  HAS  ADEQUATELY COOLED  PRIOR  TO ANY MAINTENANCE.

 

WHEN WORK IS COMPLETED,  CHECK  UNIT  PERFORMANCE IS CORRECT AND CARRY OUT ANY 

NECESSARY  ADJUSTMENTS AS  DETAILED  IN  SECTION 1.

 

After  carrying  out  any  servicing   or   exchange   of  gas carrying components -

 

ALWAYS CHECK FOR GAS TIGHTNESS!

 

 

 

3.1 GAS CONVERSION CHECK LIST

 

CHANGE MAIN INJECTORS  CHANGE PILOT INJECTORS

 

CHANGE  CROSS  LIGHTING  INJECTOR  MODIFY  MULTIFUNCTIONAL  CONTROL 

CHANGE DATA PLATE

 

To  convert  from  Natural  to  Propane  gas,  remove  regulator  mechanism.  Replace  with  blanking  plate 

supplied with conversion kit.

 

To  convert  from  Propane  to  Natural  gas,  remove  blanking  plate.  Replace  with  regulator  mechanism 

supplied with  conversion kit.

 

All  relevant  injectors  to  be  changed  to  suit  gas  type.  Adjust  pressure.  (  as  detailed  in  Sections 

1.8.&1.9)

 

3.2 BURNERS

 

Burners  should  be  cleaned  periodically  to  maintain  maximum  performance.  These  are  best  cleaned 

with  a  soft wire brush. Blocked parts require to be cleared using  a metal broach. Any material pushed into 

burner should  be shaken out via air inlet.

 

3.2.1 Removal of Burner Assembly

 

Turn  off  main  gas  supply  to  unit.  Remove  fixings  that  secure  pilot  and  cross-lighter  assemblies  to 

main  burner  and  drop  assemblies  slightly.  Disconnect  compression  joint  above  manifold.  Remove 

fixings  that  retain  burner  assembly  front  cross  strap  to  side  runners.  Pull  burner  assembly  forward 

(approx.  25mm) 

and  drop  it  slightly  to  clear  front  cross  strap.  While  supporting  weight  of  assembly, 

push it back to clear rear strap from runners  and lower to withdraw. Replace in reverse order.

 

3.2.2 Removal of Pilot Burner

 

Isolate main gas supply to unit. Disconnect pilot supply  pipe compression nut and remove pipe from pilot 

burner.  Withdraw  injector.  Undo  thermocouple  retaining  nut  and  remove thermocouple from pilot burner. 

Undo thermopile  retaining  nut  and  withdraw  thermopile.  Pull  lead  from  spark electrode.

 

Undo  nuts  that  secure  pilot  burner  bracket  to  burner.  Withdraw  pilot  burner  assembly.  Replace  in 

reverse  order.

 

 

3.3 CLEANING THE INJECTORS

 

Injectors should be periodically cleaned using a wooden  splinter or soft wire. Avoid use of metal reamers 

as these  may distort or increase size of orifice.

 

3.3.1 Removal of Main Burner Injectors

 

Isolate main gas supply.

 

Use a 10mm open-ended spanner to remove injector.

 

3.3.2 Removal of Pilot/Cross-Lighting Injectors 

Isolate main gas supply. Undo pilot/cross lighter 

supply  pipe compression nut and remove pipe from pilot/cross lighter burner.

 

Withdraw injector. Replace in reverse order. 

 

 

Содержание G3203

Страница 1: ...d be left with the Engineer in Charge for reference during servicing Further to this the Users Instructions should be handed over to the User having had a demonstration of the operation and cleaning of the appliance IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THIS APPLIANCE FAILURE TO COMPLY WITH THE SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE...

Страница 2: ...ion systems Gas water and electrical supply external to unit Light bulbs Re installing vacuum in kettle jackets Replacement of grill burner ceramics when damage has been clearly caused by misuse Where an engineer finds no fault with a product that has been reported faulty Re setting or adjustment of thermostats when unit is operating to specification Cleaning and unblocking of fryer filter systems...

Страница 3: ...1 The retaining chain has a quick release eyelet Secure to fixing point and secure bracket to floor after alignment with anti tipping device attached to the boiler Adjust to slide below floor bracket Figure 1 Anti tipping Bracket Important If appliance is to be installed in suite formation with other matching units the instructions for all models must be consulted to determine the necessary cleara...

Страница 4: ...t be smaller than gas inlet connection G3203 Rp BSP G3206 Rp BSP If flexible tube is used the gas supply tubing or hose shall comply with national requirements in force The hose shall not exceed 1 5m length These will be periodically examined and replaced as necessary An isolating cock must be located close to the unit to allow shutdown during an emergency or servicing The installation should be c...

Страница 5: ...er manifold and the operating pressure is shown in the tables below An adjustable governor is included in the multifunctional control on Natural Gas models Refer to Sections 2 6 1 setting the gas pressure and 3 7multifunctional control Supply Pressure Gas type mbar inches w g Natural Gas I2 H 20 8 Propane Gas I3P 37 14 8 1 9 2 All Models Burner Pressure Gas type mbar inches w g Natural Gas I2 H 15...

Страница 6: ...operation ensure that all packing material has been removed from unit 2 6 1 Setting The Gas Pressure It is necessary to check gas pressure during commissioning A suitable pressure gauge must be connected to test point on supply manifold a Ensure pan is filled with water b Turn on main gas valve at supply c Light burners as detailed in User Instructions The supply pipes may contain air therefore it...

Страница 7: ...ner Assembly Turn off main gas supply to unit Remove fixings that secure pilot and cross lighter assemblies to main burner and drop assemblies slightly Disconnect compression joint above manifold Remove fixings that retain burner assembly front cross strap to side runners Pull burner assembly forward approx 25mm and drop it slightly to clear front cross strap While supporting weight of assembly pu...

Страница 8: ...r to level mark Warning Filling an overheated pan with water is dangerous and may cause damage to pan structure In the event of failure with full pan replace safety stat 3 6 1 Removal of Operating Thermostat Isolate main gas supply and drain cooled water from pan Remove control knob from user thermostat and undo fixings alongside user thermostat spindle Undo control panel fixings Follow thermostat...

Страница 9: ... is sufficient SIT Nova Multifunctional Control MFC Pilot adjustment screw TH TP TH TP Burner pressure adjustment screw 3 8 GOVERNOR A governor is built in to the multifunctional control Refer to Sections 1 9 and 3 7 3 9 DOUBLE CHECK VALVE A double check valve is fitted at water inlet This component is maintenance free If a replacement is required ensure flow direction arrow points in the directio...

Страница 10: ...ation can be found on the data plate attached to base panel The following parts may require replacing during the life of this appliance Safety thermostat Spark igniter Spark ignition electrode Operating thermostat Multifunctional control MFC Thermocouple c w interrupter Thermopile Pilot assembly ...

Отзывы: