Installation & User Manual Falcon Electric, Inc.
FN2 Series OM480051 Rev.: E
36
Batteries
Battery Precautions
NEVER
discard the UPS, the UPS battery pack, or batteries in the trash. Contact your local
recycling or hazardous waste center for information on proper disposal of the used battery pack
or batteries. The depleted batteries or packs may be returned to the Falcon Service Center at
the end user’s expense for recycling. Prior to returning the depleted batteries or packs, please
contact the Falcon Service Center and obtain a Return Material Authorization (RMA) number.
NEVER
dispose of used batteries or the UPS in the trash or a landfill as it is a violation of
federal and state laws. The UPS and batteries must be recycled. For UPS and battery recycling
information, please contact the Falcon Service Center.
Battery Storage
If the UPS system is to be stored for an extended period, the following precautions should be
observed to maximize battery life:
Connect and turn on UPS to a properly rated outlet for at least 12 hours to ensure
batteries are in a fully charged state prior to long-term storage.
o
Always switch off the UPS when relocating the UPS. Be aware that, even when
disconnected, charged batteries present a risk of electric shock.
If the UPS is unused for an extended period, it must be stored in a moderate climate.
The batteries should be charged for 12 hours every 3 months by connecting the UPS to
the utility supply. Repeat this procedure every month if the storage ambient temperature
is above 25
°
C (77°F). Failure to follow this procedure can result in shortened battery life.
Battery Capacity Retention
The table below provides typical battery storage period based on ambient temperature. The
recommendations below yield about 60% battery capacity at maximum storage period. The
batteries require recharge after storage. Please reference battery manufacturer documentation.
Temperature
Maximum Storage Period
(Months)
Recommendation
5°C / 41°F
20
Good Condition.
Recharge prior to
use. (Minimum 6Hrs
to 90% capacity)
25°C / 77°F
10
30°C / 86°F
6
40°C / 104°F
3.5
50°C / 122°F
1
Содержание FN2-4.5K-2TXI
Страница 2: ......
Страница 12: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 12 Accessories Kit...
Страница 26: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 26 I1 J K L M N...
Страница 27: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 27 O O1 P O2...
Страница 29: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 29 S2 T U V1 V2 V3...
Страница 39: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 39...