Installation & User Manual Falcon Electric, Inc.
FN2 Series OM480051 Rev.: E
34
If the UPS malfunctions during operation, please check the following:
1. Verify Input / Output wiring.
2. Verify AC Input Source is within UPS acceptable voltage range.
3. If problems persist, reference the following table for possible conditions and solutions
otherwise please contact Falcon Electric, Inc. Service Department.
Error Code
Description
Er05
Battery weak or dead
Er06
Output short circuit
Er10
Inverter over-current
Er11
UPS over-temperature
Er12
Severe UPS output overload
Er14
Fan error
Er16
Output parameters set error in parallel system
Er17
ID Numbers are in conflict in Parallel System or ID
number error in single unit
Er21
Parallel communication error (communication wire
disconnected or failure to find ID1 UPS) in Parallel
S t
Er24
CVCF mode with bypass input (Bypass must be
disabled for CVCF mode.)
Er27
The UPS must be operated in normal mode in
Parallel System.
Er28
Bypass overload time out and cut off output
Er33
Isolation transformer is over-temperature
Er**
Other error codes, contact Falcon Service
Department for further assistance.
Содержание FN2-4.5K-2TXI
Страница 2: ......
Страница 12: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 12 Accessories Kit...
Страница 26: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 26 I1 J K L M N...
Страница 27: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 27 O O1 P O2...
Страница 29: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 29 S2 T U V1 V2 V3...
Страница 39: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 39...