____________________________________________________________________________
- 23 -
Table 3-1 Set Menu Layout
System
IP
Default 192.168.1.123
S-Mask
Default 255.255.255.0
Baud
Serial port baud rate, 4800/9600/19200/38400/115200, default: 9600.
Parity
None/odd parity/even parity, default: None
Sound
Keyboard sound ON/OFF. Default: ON
Language
Simplified Chinese/Traditional Chinese/English. Default: English.
Shortcut
Fast recall function ON/OFF. Default: Off
Power Save
Power down save function ON/OFF. Default: ON
Power Output
Define power supply output On/Off state at its power on moment. Default: Off
Output
V_MAX
Upper limit of static output voltage set , default 0 means no limit
V_MIN
Lower limit of static output voltage set, default 0 means no limit
I_MAX
Upper limit of static output current set, default 0 means no limit
I_MIN
Lower limit of static output current set, default 0 means no limit
VDC_R
Set rise voltage threshold in DC_ON function, refer to “3.7.2 DC_ON Set”
VDC_F
Set fall voltage threshold in DC_ON function, refer to “3.7.2 DC_ON Set”
TTL
Set DC_ON function output TTL level signal, refer to “3.7.2 DC_ON Set”
Vslew
Set Voltage slew rate, range: 0.001V/s~5000V/s
Islew
Set current slew rate, range: 0.001A/s~2000A/s
Prior
Choice for CV or CC priority. Default value: Voltage (CV Priority)
Protect
OVP
Set overvoltage protection point, default value 110% rated output voltage
OCP
Set overcurrent protection point, set 0 to turn off this protection, default 0
OPP
Set overpower protection point, set 0 to turn off this protection, , default 0
Foldback
Select foldback protection mode, OFF / CC-to-CV / CV-to-CC, default set OFF
F_Time
Set foldback delay time, default 0.1s
RVP
Turn on/off reverse voltage protection, default value: OFF
LVP
Set low voltage protection point, default set 0 to turn off this protection.
Over time
Set communication time out, range: 0.0~60.0s, set 0 to turn off this protection;
External
Inhibit
Choose external control mode, Off/Toggle/Hold, default: OFF
APG
Choose external programming mode, Off/U/I/U+I/P, default: Off.
Vref
Select reference voltage, 5V/10V, default: 5V
DEVI-ADDR
Set device address
Protocol
Set protocol
Filter
Set voltage/current data acquisition speed in remote communication
GPIB
Set GPIB address