background image

9

MASONARY THIMBLE

3" CLEARANCE TO

COMBUSTIBLE

24"

PL VENT TEE

WITH CLEANOUT

CAP

STORM

COLLAR

ALWAYS FOLLOW PL VENT 
MANUFACTURERS CLEARANCES
TO COMBUSTIBLES

FLASHING

CEILING OR 

WALL THIMBLE

3" CLEARANCE TO

COMBUSTIBLE

PL VENT TEE

WITH CLEANOUT

Venting into an Existing chimney

combustion air

1. If the furnace’s exhaust is connected to a masonry chimney, 

the masonry chimney must be free of cracks that could leak 

exhaust gases or fly ash. a relining of the chimney with ei-

ther PL vent or single wall stainless steel pipe may be neces-

sary to bring the chimney into compliance.

2. When chimneys are relined, a chimney chase cap that 

reduces the outlet of the chimney to the size of the liner is 

required. Extend the exhaust vent above the chimney chase 

cap and finish it off with a rain cap. a single wall liner may 

need to be wrapped with insulation to maintain adequate 

exhaust temperatures when outside temperatures drop be-

low freezing, causing the flue temperatures to become too 

low.

3. Venting into the side of an existing masonry chimney must 

be done through a masonry thimble. When wall penetration 

is necessary to access a masonry chimney, use a listed PL 

vent wall thimble. chimney connectors should be made with 

minimum 24 Gauge black or blue steel.

4. When venting into a Class A steel chimney, use an appro

-

priate PL Vent adapter.

The 50F furnace may be connected to an existing class a chimney or a masonry chimney which meets the 

minimum requirements of nFPa 211.

• Outside air is required. 

• Outside air may be drawn from a semi-enclosed attic or 

crawl space or any semi-enclosed space. Take care not to 

draw cold air past water pipes that may freeze.

• Use 3" or greater flexible or rigid metal piping.

• Terminate the outside air pipe below the exhaust vent outlet.

• An open mesh screen should be placed over the outside air 

pipe opening to prevent birds or rodents from nesting in the 

opening. Use an elbow or shield to prevent prevailing winds 

from blowing directly into the outside air intake pipe. NOTE: 

Mesh screen should be no smaller than one-fourth inch 

(1/4") by one-fourth inch (1/4").

Figure 6

EndURancE 50F   

vENTING INTO AN EXISTING ChIMNEY

NOTE: The outside air pipe must terminate above the 

maximum snow line. Long runs should be avoided.

     WARNING

Outside combustion air is required for  

all installations!

     WARNING

Use the air intake damper for adjusting combustion inlet air only! Other methods of restricting or blocking 

combustion inlet air are strictly prohibited!

Figure 7

Air Intake 

Damper

Содержание Endurance 50F

Страница 1: ...redited These installation instructions must be strictly observed Failure to follow instructions may result in property damage bodily injury or even death Please read this entire manual before install...

Страница 2: ...your new furnace Failure to follow instructions may result in property damage bodily injury or even death CAUTION Failure to follow the instructions in the installation manual may result in a house f...

Страница 3: ...ontrol Board Features Mode and Operating Description 16 Control Board Operation 17 Auto Ignition 18 Manual Ignition 19 Error Descriptions 19 Combustion Air Damper Box 20 Adjustments 21 Cleaning Requir...

Страница 4: ...for shipping These bolts can be used for mobile home installation The front door handle will need to be installed with the screws provided See figure 2 For use in the U S and Canada mobile home appro...

Страница 5: ...ntroller also monitors this Once the set amount has been reached the unit will cycle in the cast re light plate The fuel now falls on this plate and is ignited by the lower flame After it is ignited t...

Страница 6: ...um clearance from combustibles and to allow for furnace maintenance Front 24 minimum clearance from combustibles and to allow furnace maintenance Back Side 6 minimum clearance from combustibles and or...

Страница 7: ...be used inside an existing chimney No clearances to combustibles are needed on sin gle wall stainless steel adapters rigid or flex pipe installed within a chimney A clean out tee PL vent or Quick Conn...

Страница 8: ...p a con centration of fumes 3 Vent surfaces can get hot enough to cause burns if touched by children Non combustible shielding or guards may be required Figure 4 4 1 2 m BELOW a door window cavity or...

Страница 9: ...e a listed PL vent wall thimble Chimney connectors should be made with minimum 24 Gauge black or blue steel 4 When venting into a Class A steel chimney use an appro priate PL Vent adapter The 50F furn...

Страница 10: ...ave a minimum temperature rating of 250 F The plenum of the 50F furnace must be constructed of metal This unit is not to be connected to a chimney flue serving another appliance Once installed check t...

Страница 11: ...t must be used for exhaust venting Single wall vent is not allowed Follow PL vents manufacturer s installation di rections and observe all listed clearances to combustibles WARNING Do not install in a...

Страница 12: ...determine a neutral location to mount the thermostat for accurate room temperature measurements NOTE For installations requiring an external thermostat the 50F furnace must be connected to an approved...

Страница 13: ...sorb moisture from damp or wet floors This will also prevent rodents from becoming a problem Do not store fuel within furnace in stallation clearance areas or within the space required for ash removal...

Страница 14: ...iculty adjusting the 50F furnace contact your dealer or technical support 6 To avoid the possibilities of smoke and or spark entering the room always keep fire chamber door and ash pan drawer secured...

Страница 15: ...BLED WHILE SELF CLEANING IS IN PROGRESS B Menu Returns the screen to the Menu C Prime Allows the user to manually feed fuel into the burn pot on start up when needed This is particularly helpful in pr...

Страница 16: ...Clean Complete Light 2 cups pellets with gel and wait 3 minutes See Quick Start Guide ENTER Done CONTROL BOARD OPERATION Stabilizing LEVEL 3 Fuel 10 P Pellet Vacuum Flame Auger Running LEVEL 3 Fuel 1...

Страница 17: ...Settings The LCD Control Panel will display the MENU of default set tings To change a setting use the UP and DOWN arrows to select the menu item then ENTER to select the options etc 5 Press the ON OF...

Страница 18: ...ions etc 5 Press the ON OFF Button to Start Once the settings are correct for your fuel type etc push the ON OFF Button for approx 1 second The LCD screen will display what process is running Current...

Страница 19: ...d shape Verify the incoming combustion air and the exhaust is free of any debris that could interrupt air flow Insure air damper is open and Sail switch is swinging open by looking into the damper ope...

Страница 20: ...ations If you experience problems adjusting the 50F furnace during the break in period contact your dealer Some chimney systems have abnormal characteristics which can take time to adjust For instance...

Страница 21: ...eaning Prolonged burning at a slow burn rate will result in the need for more frequent window cleaning It is recommended to clean the window when the unit is cold however it is possible to clean the d...

Страница 22: ...leaning of the exhaust sys tem is required Under certain conditions chimneys may plug up rapidly Dirty high moisture content fuel and poor installations require more frequent chimney cleanings See the...

Страница 23: ...to actuator slides 4 The exhaust fan should be cleaned may require a new gas ket Call dealer for this service Annual oiling of the motors is not needed See Figure 15 Fall Startup 1 Prior to lighting...

Страница 24: ...allowed time to cool Positioning Parts for Removal 1 Enter maintenance mode from the Main menu Current Setting 2 Select Auto Pot Removal 3 Close all doors and press Enter 4 Wait for pot parts to be po...

Страница 25: ...e 19 10 Remove the Flapper Door Assembly by lifting upward Figure 20 11 Remove the Burn Shell by lifting up and out Figure 21 Installation of Pot Parts Reverse of steps 6 thru 11 above Figure 21 Figur...

Страница 26: ...When removing the screws take care not to drop the screws between the panels of the unit Remove wire con nectors and carefully remove Igniter and Tube Assembly as shown in Figure 23 3 Remove two lowe...

Страница 27: ...oroughly cooled 2 Never use gasoline or gasoline types such as lantern fluid kerosene charcoal lighter fluid or similar liquids to start or improve a fire in this furnace Keep all such liquids well aw...

Страница 28: ...atic Endurance 50F wiring schematic The electrical rating for this furnace is 115 Volt 60Hz 4 AMP The minimum circuit is 15 AMP CAUTION Call your local dealer for diagnostics and replacement of electr...

Страница 29: ...sary in mild weather even though monthly cleaning may be enough in the coldest months Run the furnace on the hottest setting once a day for 30 45 minutes to pre vent excessive build up in the furnace...

Страница 30: ...nd after installation of this add on furnace by a gas fitter that is recognized by the regulatory authority 8 Do not connect to any gas furnace that is not equipped with an air circulating blower or t...

Страница 31: ...left open longer than 90 seconds b The ash pan door was left open longer than 90 seconds c Switch is defective d Intake air or exhaust path obstructed e Seals need replacing Solution Check inner door...

Страница 32: ...ily and Periodic Maintenance section of the manual If the furnace still does not operate correctly call your dealer for assistance 11 My Furnace isn t burning and the controller is displaying AUGER TI...

Страница 33: ...all costs related to shipping the replacement parts or return of the unit to the factory for replacement If the defect was caused by Fahren heit Technologies Inc then Fahrenheit Technologies Inc will...

Страница 34: ...End Assembly 15 CS1 1390 Sail Switch Assembly 16 CS1 1501 Hopper Top 17 CS1 1505 Lid Switch Arm Item Part Number Description 18 CS1 1550 Top Panel Assembly 19 CS1 2000 Exterior Door Assembly 20 CS1 3...

Страница 35: ...n Gasket 53 CS1 9421 Spider Coupler 54 CS1 9444 Auger Motor 55 CS1 9445 Auger Item Part Number Description 56 CS1 9446 Bronze Bushing 57 CS1 9449 3 8 Coupler 58 CS1 9502 Exhaust Blower Gasket 59 CS1 9...

Страница 36: ...Save This Manual For Future Use Tested to UL391 Standards 526 East 64th Street Holland MI 49423 www fahrenheittech com...

Отзывы: