background image

 

Page 7/9 

 

Fault diagnosis

 

3

 

Fault diagnosis 

VISY

-

Output

 

1 has several LEDs to make diagnosis easier when there are problems. The 

position of the LEDs can be seen in Figure 1.

 

 

3.1

 

Relay LED (3) 

The red LED for the relay shows whether the relay is energised or deenergised (active or 

passive).

 

 

3.2

 

Status LED (4) 

The yellow status LED gives information on the status of communication between the VI

-

... 

interface card in the VISY

-

Command and the VISY

-

Output

 

1.

 

The following table lists the possible states of the status LED and explains their meaning.

 

Status LED

 

Fault

 

Meaning

 

On

 

No error

 

C

orrect data is being received regularly

 

C

ontinuous flash

 

N

o communication

 

N

o correct data received since the last switch

-

on

 

1 short flash

 

C

ommunication 

 

interruption

 

N

o correct data received for longer than 1 

minute

 

2 short flashes

 

H

old time exceeded

 

No correct data received for longer than the 

configured 

hold time

 

Table 2: Status LED

 

 

Under normal conditions, the status LED should be on constantly. 

 

3.3

 

Operating voltage LED (5) 

The green operating voltage LED shows whether the VISY

-

Output

 

1 is being supplied with 

power. After the auxiliary energy is turned on, the operating voltage LED glows contin

u-

ously. An LED that flickers or goes out indicates a problem with the auxiliary energy or the 

electrical adaptor.

 

 
 

 

Содержание VISY-Output 1

Страница 1: ...IR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 39 82 07 0 Fax 49 40 390 63 39 Technical documentation VISY Output 1 1 Channel Relay Output Module Version 2 Edition 2016 09 Art No 350...

Страница 2: ...I Table of contents Copyright Reproduction and translation are permitted only with the written consent of FAFNIR GmbH FAFNIR GmbH reserves the right to make changes to products without prior notice...

Страница 3: ...2 3 6 Connection to the VISY Command 3 2 4 Configuration 4 2 4 1 Hold time after communication loss 4 2 4 2 Behaviour of the output after the hold time has expired 5 2 4 3 Relay mode 5 2 4 4 Relay de...

Страница 4: ...utput 1 is intended for use within the VISY X system only Modifications to the VISY Output 1 are prohibited without the prior consent of the manufacturer All installation and maintenance work except f...

Страница 5: ...one side of the module holder is fixed in place Then press the other side of the module carrier onto the rail until this side snaps in and the module carrier sits firmly The VISY Output 1 can be used...

Страница 6: ...contacts The VISY Output 1 has a relay with a potential free changeover contact An external safety device or alarm indicator can be connected to the terminals marked NO C NC of the 3 pin screw termin...

Страница 7: ...ation adjusts the VISY Output 1 to the requirements of the relevant application The following settings are possible 1 Hold time after communication loss 2 Behaviour of the output after the hold time e...

Страница 8: ...assive when the output is activated The fail safe mode offers the advantage that even if the auxiliary energy of VISY Output 1 fails an alarm signal can be sent via the relay that is then going passiv...

Страница 9: ...t due to a still incomplete configuration The maintenance mode is turned on and off using the VISY Setup configuration software if this function is supported The maintenance mode automatically stops a...

Страница 10: ...LED Fault Meaning On No error Correct data is being received regularly Continuous flash No communication No correct data received since the last switch on 1 short flash Communication interruption No...

Страница 11: ...NIR customer service 5 Technical data Dimensions H 76 x W 24 x D 47 mm Housing protection None Ambient temperature 0 C 40 C Power supply 5 VDC 40 mA supply through VI 4 Communication With VI 4 through...

Страница 12: ......

Страница 13: ...Blank page...

Страница 14: ...Blank page...

Страница 15: ...Blank page...

Страница 16: ...FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 39 82 07 0 Fax 49 40 390 63 39 E mail info fafnir de Web www fafnir de...

Отзывы: