UM-X
Page 19/35
6.5.3
6.5.3
6.5.3
6.5.3
6.5.3 Settings menu S-P Off (switching-off point)
Settings menu S-P Off (switching-off point)
Settings menu S-P Off (switching-off point)
Settings menu S-P Off (switching-off point)
Settings menu S-P Off (switching-off point)
The "S-P Off" (Switching Point Off) menu shows you the
value at which the relay is deactivated.
The switching-off point is specified in percent in steps of 0.1
percent. The range of values is 0.1 to 99.9 percent. The
millimetre, inch and milliampere units are calculated and
displayed for information.
Using the functions
[+] PLUS and
[-] MINUS
you specify the switching-off point. Confirm your selection
with RETURN [
] .
The current value must not be less than 4 mA and must not be more
than 20 mA so that malfunctions do not occur.
The following information applies only to relays K1 and K2:
For the UM-O and UM-O Ex equipment versions (overfill prevention),
you need a password for changing the switching-off point.
The range of values for these versions is between 0.1 and 99.0 percent.
The switching-off point (S-P Off) is always higher than the switching-
on point (S-P On) and can never be lower than this.
6.5.4
6.5.4
6.5.4
6.5.4
6.5.4 Settings menu On Delay
Settings menu On Delay
Settings menu On Delay
Settings menu On Delay
Settings menu On Delay
You define the 'On Delay' of a relay in the "On Delay"
settings menu.
The delay time can be between 0 and 255 seconds and is
specified in 1-second steps.
Using the functions
[+] PLUS and
[-] MINUS,
you enter the value. Confirm your selection with
RETURN [
] .
Fig. 10:
"On Delay" display
Fig. 9:
"S-P Off" display