 Once satisfied that voltage is properely supplied to the system, and provided that the LEDs of the limit switches are  correctly 

switched (post down L8 is OFF), by the first pulse the post should rise, if not swap the motor live connections (in Elpro S40)         
after voltage supply to the system has been switched off.

ATTENTION: a 40 µF capacitor is pre-wired inside the junction box. For the Talos option 4 mm thickness (steel 
and inox/stainless steel) do NOT connect any more capacitors to the terminals A and B of the Elpro S40 
controller unless required to achieve a good performance of the bollard. For the Talos option 12 mm thickness 
a 20 µF capacitor is required to be added to the terminals A and B of Elpro S40.

common

common

connections to the electric motor

of the hydraulic motor pump

Bollard raised:

 gateway closed

1° pulse

If the application requires more than one bollard, go through all of the steps with each

Pic. 17

FIXING THE COVER PLATES OF THE BOLLARD

NOTE WELL: BOLLARD AND COVER PLATE ARE TO BE 
PERFECTLY CENTERED, SO THAT THE GAP  BETWEEN 
BOLLARD AND COVER PLATE HOLE IS EQUALLY 
SPACED ALL AROUND

The cover plate is to firmly rest all over the 

surface and closely adhere to the circular flange 

around the post

Pic. 18

Pic. 19

GREASE

NOTE WELL: IT IS RECOMMENDED 
THAT ALL OF THE FIXING SCREWS 
BE GREASED

Retractable Oil-hydraulic Bollard

English

13

Содержание TALOS Series

Страница 1: ...BOLLARD WITH RETRACTABLE CYLINDRICAL POST OIL HYDRAULICALLY OPERATED GB Instructions manual pages the gate opener 1 20 EN 13241 EN 12453 EN 12445...

Страница 2: ...e safety accessories such as photocells sensitive edges etc Carry out a risk analysis by means of appropriate instruments measuring the crushing and impact force of the main opening and closing edge i...

Страница 3: ...an area The TALOS series includes a vast selection of options as indicated below varying in height thickness and depth of embedding constraint for impact resistance the abbreviation HRC identifies th...

Страница 4: ...triangular socket end Post cover with rubber edge n 9 Led lights flashing amber in colour Back reflecting sticker with logo Box to house the electric cable from the electronic controller Cover plate C...

Страница 5: ...supply cable 9 Post for Fit 55 photocell projector 10 Oil hydraulic bollard Talos series 11 Vix 53 remote control transmitter 12 Post for Fit 55 photocell receiver 13 Visual 344 post to take command a...

Страница 6: ...own into the pre holed seats NOTE WELL make sure the ground cable is disconnected from the casing before lifting Carefully hoist and remove the inner assembly of the bollard by a winch Make sure the c...

Страница 7: ...ead the electric cables through it from a junction box or directly from the electronic controller Elpro S40 Pic 6 NOTE WELL the foundation casing is to be set perfectly levelled and the upper edge mus...

Страница 8: ...r than the surrounding walking surface in order to limit the amount of water that may get inside it Cast concrete all around the casing up to 5 10 cm from walking level Wait all the time required for...

Страница 9: ...al see catalogue Pre assembled loop 12 metres circumference optional see catalogue Power supply cable max 10 metres pre fitted to the loops Detector for metallic masses See the instructions supplied w...

Страница 10: ...allation as required either for public or private users and in compliance with the existing safety norms A screw is provided for proper connection For applications in public areas use a cable having a...

Страница 11: ...B of the Elpro S40 controller unless required to achieve a good performance of the bollard For the Talos option 12 mm thickness a 20 F capacitor is required to be added to the terminals A and B of El...

Страница 12: ...he electric power is supplied check the status of the LEDs first of all as follows with the post in down posistion the L8 LED must be OFF while L9 must be ON if not swap the connections to terminals 1...

Страница 13: ...nce of the bollard For the Talos option 12 mm thickness a 20 F capacitor is required to be added to the terminals A and B of Elpro S40 common common connections to the electric motor of the hydraulic...

Страница 14: ...HE POST BE ASSISTED TO REACH THE FULLY FLAT DOWN POSITION Retractable Oil hydraulic Bollard English Pic 21 Pressure switch adjustment 1 Unscrew the M5 pin 2 Adjust the sensitivity using an allen key s...

Страница 15: ...pment to release the unit and allow manual lowering ATTENTION once the post has been manually lowered rising can be made possible only by powering the system and pulsing it to rise Pic 23 Help the pos...

Страница 16: ...tion date Quantity of models installed Maintainer Date NOTE WELL this document must record any ordinary and extraordinary services including installation maintenance repairs and replacements to be mad...

Страница 17: ...ic board controlling the bollard s e g flooded relay contacts oxidized terminal clamps etc Check the correct functioning and positioning of the limit switches Check the release system for bollard manu...

Страница 18: ...interfere with it 6 Make sure that electromagnetic sources are at a suitable distance from the accessories especially from the loop detectors The magnetic fields of other sources might affect the dete...

Страница 19: ...ion impact resistance 90 000 J breakout resistance 550 000 J Static load max 1 500 kg in standing position max 20 000 kg in lowered position Working temperature 40 C 80 C Supply voltage 230 Vac 10 50...

Страница 20: ...out 12 Vdc 600mA LED lights 12 Vdc Post material S235JRH 4 mm steel S355J2H 12 mm steel AISI 304 inox AISI 316 inox brushed SS steel standard HRC Impact resistance thick 4 52 000 J 70 000 J Crash resi...