page 14
AUTOMATIC / SEMI-AUTOMATIC:
Automatic cycle:
by one pulse from the open command the gate opens and stops in
dwell mode for the time as pre-set on the
dwell trimmer
. When this time expires the gate
closes automatically.
Semi-automatic cycle:
by one pulse from the open command the gate opens and
stops in fully open position. To close the gate, a close pulse is needed.
Dip-switch setting and LED indication of functions
Dwell trimmer:
adjust dwell time
on automatic mode from
1s up to 220s
3
ON
: Automatic closing
OFF
: Semi-automatic, closing by pulse
DIP-SWITCH-A N°3:
Description
DIP-SWITCH-A N°8:
PEDESTRIAN OPENING:
With the gate in fully closed position, a pulse to terminals
P-P operates the gate for pedestrians.
(On pedestrian mode, it is advisable to set Dip-A N°3= ON
for automatic re-closing).
The function
"pedestrian opening"
is not in service during
the first operation cycle, after a power failure.
9
ON:
DSA safety control enabled
OFF:
DSA safety control disabled
DIP-SWITCH-A N°9:
DEADMAN (HOLD-ON-SWITCHED) CONTROL:
The open/close operations are achieved by " holding on a command
switched " (the relays are not self-holding) and consequently the user must
be actively present during gate movements until the push-button or the
key-switch is released.
6
ON:
Deadman control enabled
OFF:
Deadman control disabled
DIP-SWITCH-A N°6:
3
DIP-SWITCH-A N°3:
3 4
24V ac output
for photocell TX
enabled for
DSA control
38 39
FUNCTIONS FOR SLIDING GATE OPENING
PARTY FUNCTION
OPEN-AND-HOLD BY EXTERNAL CLOCK:
Connect the clock NO contact to OPEN terminals
No. 4 and COMMON No. 3, and activate automatic
closing by setting dip-switch No. 3=ON.
How it works: program the opening time on the clock.
At the preset time, the gates will open and remain
open (the flashing light will turn off) and will not accept
any other command (not even radio commands)
until the time set on the clock expires.
When this time expires the gates close automatically
after the pause time.
While the gates are held open by the time set on the
"clock", the indication light keeps giving out two
consecutive flashes followed by a long pause.
-
+
DSA: PHOTOCELL AUTOMATIC CONTROL:
For the
DSA
control (
D
evice for
S
afety
A
uto-test) it is necessary to
connect
only the photocell transmitters (TX)
to this output and
select
dip-A No.9=ON
: if this function is enabled, ELPRO 37 DS checks
that all the connected photocell devices are cleared from obstacles
and properly working before starting any door/gate movements,
otherwise the door/gate is not started.
RE-CLOSING BY PASSING ACROSS THE PHOTOCELLS: in opening and dwell cycles
(DIP-A N°3=ON)
Gate is automatically closed after 3s from passing between the photocells.
L0 OFF =
no pedestrian contact given,
it goes on by pulsing for pedestrians
1 2 3 4 5 6
OPEN
PEDESTRIANS
8
ON
: Automatic closing on passing across
the photocells after 3 seconds
OFF:
No automatic closing on passing
across the photocells
COMMON
NO
External Clock
ON:
Automatic closing
OPEN
COMMON
IMPORTANT: use always and only with
Dip-A N°3= ON
-
+
PEDESTRIAN
OPENING
1s - 45s
SINGLE – THREE PHASE ELECTRONIC CONTROL BOARD WITH ELECTRONIC BRAKE FOR
DOUBLE-LEAF SLIDING GATE AUTOMATIC SYSTEMS WITH OR WITHOUT LIMIT SWITCHES
meccanica
FADINI
GB
37
DS