7

6

PIC. 12

PIC. 14

- Fix the 

electro-hydraulic motor pump unit

 by means of expanding

bolts (not included). It is to be fixed close to the gate to operate
in the most suitable position considering all the fitting, setting and
testing operations involved.

- Excavate between the 

jack

 and the 

motor pump

 (Pic.12) and lay

a tube  to house the pipes: copper pipes are supplied on request
in one length to be bent on site to meet the application requirements.

- Assemble the 

enclosure

 around the 

jack

 and fix it with concrete.

Fill in the whole escavation from the hole where the 

jack

 is located

to the 

motor pump unit

 where the pipes are laid.

FILLING THE MOTOR PUMP WITH POWER OIL

- Unlock the 

motor pump front cover

 by the provided key and remove

it. Incorporated in the 

motor pump unit

 is a 

funnel

. Pull it outwards

(2 cm approx.) and turn it up (Pic. 13).

- The power oil, supplied with the equipment in a 3 

l

 container, is to

be poured up to the sight glass.

HYDRAULIC
MOTOR
PUMP UNIT

HYDRAULIC
JACK

FIXING
BOLTS

OIL-HYDRAULIC
JACK

PIPE CONDUIT

ENCLOSURE

GRAVEL  LAYER TO
PROVIDE A SOAKAWAY

FRONT COVER

HYDRAULIC
MOTOR PUMP
UNIT

HYDRAULIC
JACK

HYDRAULIC
MOTOR PUMP
UNIT

PIPES

KEY

NUT

SPIGOT

3 mm

ELBOW
FITTING

PIC. 11

PIC. 13

FUNNEL

POWER SUPPLY
CABLE

IMPORTANT

: Avoid sharp bending in the pipes between the motor pump unit and the jack; make sure that all nuts  in the jack and motor

pump are well tightened.

ELECTRICAL CONNECTIONS TO ELPRO 13 CEI CONTROL PANEL

Before carrying out any electrical connections read the enclosed electrical wiring diagrams (Pic.15).

IMPORTANT

: All the equipment must be properly 

earthed

 (Pic.15).

- The 

mains, electric motor and flashing lamp

 wires must have a 1.5 mm

2

 square section for a max. distance of 50 m in case that a

longer distance is required,  section must be 2 mm

2

.

- 1 mm

2

 square  section wires can be used for the 

accessories

 such as the 

photocells, keyswitch etc.

FITTING THE ELECTRIC LOCK, THE MECHANICAL LATCHING BOLT AND THE GATE STOPS

It is recommended to fit the gates with an electric lock  either vertically or horizontally positioned (70 cm high from ground level in the
second case) in order to  better hold the gates in the closed position. The gate that is fitted with the electric lock is to be 5 degrees out of
phase against the other one and has to reach the stop closed position  a bit later than the gate that is fitted with the catching plate. In the
case where the gate lock is horizontally fitted, it is also needed to fit a latching bolt to the gate that first reaches the gate stop. The bolt is
latched into the gate stop by the other ie. the delayed gate on approaching the gate stop (Pic.14).

IMPORTANT: Provide the installation with gate stops in the open gate position to be fixed 5

°

 before the jack reaches the very end of the

permitted stroke.

FIT THE HEAD OF THE GATE THAT CLOSES FIRST WITH A LATCHING BOLT
TO BE DRIVEN INTO  THE CLOSED POSITION GATE STOP WHERE A HOLE
HAS BEEN PROVIDED FIRST

GATE STOP
CLOSED POSITION

THIS GATE
CLOSES
FIRST

LATCHING BOLT

70 cm

THIS GATE
CLOSES FIRST

DELAYED
GATE

HORIZONTAL
ELECTRIC LOCK

VERTICAL ELECTRIC
LOCK

HORIZONTAL ELECTRIC
LOCK  CATCHING PLATE
IIN CLOSED POSITION

70 cm

GATE STOP
OPEN
POSITION

90

°

95

°

1) MIRI 4 FLASHING LAMP
2) ELPRO 13 CEI CONTROL PANEL
3) O.O3 A MAGNETIC-THERMAL CIRCUIT

BREAKER

4) JUNCTION BOX
5) DRIVE 700 MOTOR PUMP UNIT
6) DRIVE 700 JACK
7) POLO 44 PHOTOCELL RECEIVER

8) ELECTRIC LOCK
9) POST-MOUNTED POLO 44 PHOTOCELL PROJECTOR
10)POST-MOUNTED POLO 44 PHOTOCELL RECEIVER
11)POLO 44 PHOTOCELL PROJECTOR
12) JUBI 433 EXTERNAL RADIO RECEIVER
13) BIRIO A 8 AERIAL
14) PRIT 19 KEYSWITCH
15) JUBI 433 TRANSMITTER

1

2

3

4

5

6

7

5

8

9

10

11

12

6

13

14

15

230 V
50 Hz

n

°

2x1.5

n

°

4x1

n

°

2x1

n

°

2x1

n

°

4x1

n

°

4x1.5

n

°

2x1

n

°

4x1

RG58

 cable

n

°

4x1

n

°

4x1.5

n

°

4x1.5

GATE STOP IN
OPEN GATE
POSITION  AT 95

°

GATE STOP IN
OPEN GATE
POSITION AT 90

°

GATE STOP IN
CLOSED GATE
POSITION

90

°

95

°

PIC. 15

OIL LEVEL
SIGHT GLASS

Содержание DRIVE 700

Страница 1: ...stroke 52mm Working temperature 20 C 80 C Oil volume 0 25dm3 Static gate weight 700Kg PERFORMANCE Duty cycle 23 s Opening 30 s Dwell 23 s Closing Time of one complete cycle 76s No of complete cycles O...

Страница 2: ...stem PIC 2 DRIVE 700 PIC 1 GATE STOP IN OPEN GATE POSITION ENCLOSURE GUIDE BASE PLATE FIXING ANGLES FIXING BASE PLATE ENCLOSURE LID NERROW SECTION ENCLOSURE LID LARGE SECTION MOTOR PUMP UNIT MOTOR PUM...

Страница 3: ...stem PIC 2 DRIVE 700 PIC 1 GATE STOP IN OPEN GATE POSITION ENCLOSURE GUIDE BASE PLATE FIXING ANGLES FIXING BASE PLATE ENCLOSURE LID NERROW SECTION ENCLOSURE LID LARGE SECTION MOTOR PUMP UNIT MOTOR PUM...

Страница 4: ...position and the setting is maintained for long time By means of a wrench rotate the jack shaft until you can feel that the limit of the permitted stroke in closed gate position is reached in this po...

Страница 5: ...position and the setting is maintained for long time By means of a wrench rotate the jack shaft until you can feel that the limit of the permitted stroke in closed gate position is reached in this po...

Страница 6: ...as the photocells keyswitch etc FITTING THE ELECTRIC LOCK THE MECHANICAL LATCHING BOLT AND THE GATE STOPS It is recommended to fit the gates with an electric lock either vertically or horizontally pos...

Страница 7: ...as the photocells keyswitch etc FITTING THE ELECTRIC LOCK THE MECHANICAL LATCHING BOLT AND THE GATE STOPS It is recommended to fit the gates with an electric lock either vertically or horizontally pos...

Страница 8: ...if mounted outside a suitable enclosure is recommended to protect it from sunshine and rain 2 Bridge terminals 1 2 if you do not require any photocells 3 Should two sets of photocells be required thes...

Страница 9: ...if mounted outside a suitable enclosure is recommended to protect it from sunshine and rain 2 Bridge terminals 1 2 if you do not require any photocells 3 Should two sets of photocells be required thes...

Страница 10: ...ulic motor pump units both gates are to be operated in the same direction Should they fail to perform in a synchronized way swap the electrical motor connections ie live 1 and 2 for both gates to open...

Страница 11: ...ulic motor pump units both gates are to be operated in the same direction Should they fail to perform in a synchronized way swap the electrical motor connections ie live 1 and 2 for both gates to open...

Страница 12: ...stroke 52mm Working temperature 20 C 80 C Oil volume 0 25dm3 Static gate weight 700Kg PERFORMANCE Duty cycle 23 s Opening 30 s Dwell 23 s Closing Time of one complete cycle 76s No of complete cycles O...

Отзывы: