manualshive.com logo in svg
background image

 

General  Description 

Pre-Installation Information 

To the Installer: If you are familiar with the installation, you can jump to section 

4 - Installing the TAS250

 or use the 

Appendix A - Installation Checklist on page 31

 of this manual. 

Safety Instructions 

Important: 

NEVER INSTALL THE EQUIPMENT DURING A LIGHTNING STORM! 

This equipment, FAAC Telephone Access System, shall be installed and used within an environment that provides 
the  pollution  degree  max  2  and  over  voltages  category  II  NON  HAZARDOUS  LOCATIONS,  INDOOR  and 
OUTDOOR.  The  equipment  is  FIXED  and  PERMANENTLY  CONNECTED  and  is  designed  to  be  installed  by 
Service  Persons  only;  [service  person  is  defined  as  a  person  having  the  appropriate  technical  training  and 
experience  necessary to be aware  of hazards to  which that person may be exposed in performing a task and of 
measures  to minimize the risks to that person or other persons.] The equipment is installed in a metallic cabinet 
that meets the applicable requirements for a FIRE ENCLOSURE. 

1.The 

connection to the mains supply

 must be made as per the local authorities rules and regulations 

An appropriate disconnect device must be provided as part of the building installation. Where it is  
not possible to rely on the identification of the NEUTRAL in the AC MAINS SUPPLY, the disconnecting device must  
disconnect both poles simultaneously (LINE and NEUTRAL). 

• 

Be permanently connected, fail safe, with double or reinforced insulation between primary and secondary 

circuits. 

• 

The  ground  connection must  be provided by  the TERMINAL BLOCK  at the PE (IEC 60417-5019 symbol) 

marked  connection.  It  is  the  installer’s  responsibility  to  provide  protection  against  a  short  circuit  on  the 
input (bridge rectifier, C2, etc.). 

• 

The  system  requires  the  integrity  of  the  subscribed  telephone  line  to  be  operational  at  all  times.  If  the 

telephone line is cut off, placed out of service, or shared with other interconnect telephone devices other 
than the TAS250, the unit will not be able to perform its function when required. 

2.AVOID 

setting up

 the equipment near heaters, air conditioners, ventilators. DO NOT select a place that exposes  

the TAS250 to vapors, chemicals or dust. 

3.If 

during the installation

 a knockout on the cabinet is removed, it is the installer's responsibility to ensure that the  

same degree of protection for the cabinet is provided by the use of bushings, fittings, adequate sealant, etc. 

4.The metallic 

cabinet must be secured to the building structure before

 operation. 

5.The 

ground connection

 must be as shown within the included diagram, or equivalent. 

6.

Internal wiring

 must be routed in a manner that prevents: 

• 

Excessive strain on wire and on terminal connections; 

• 

Loosening of terminal; connections; 

• 

Damage of conductor insulation. 

7.It is the end-user and/or installer's responsibility to ensure that the disposal of the used batteries is made according  

to the waste recovery and recycling regulations applicable to the intended market. 

8.There are 

no serviceable parts within the equipment

; For any issues regarding the equipment please contact  

your installer. 

9.

CAUTION

: To reduce the risk of fire, use only AWG #26 or larger telecommunication line cord. 

10.

CAUTION

: Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the  

instructions. 

11.

Sealant application

 is required on all mounting holes and removed knockouts. The draining holes must 

not

 be  

blocked by any excess of sealant. 

12.

DISCONNECT POWER BEFORE SERVICING

Содержание TAS250

Страница 1: ...quarter East Coast Operations 5151 Sunbeam Road Suites 9 11 Jacksonville FL 32257 Tel 866 925 3222 www faacusa com FAAC International Inc West Coast Operations 357 South Acacia Avenue Unit 357 Fullerton CA 92831 Tel 800 221 8278 ...

Страница 2: ......

Страница 3: ...hitecture 11 2 Technical Specifications 15 3 Electrical Specifications 16 4 Installing the TAS250 17 4 1 Preparing to Install the TAS250 17 4 2 Installation 17 5 Troubleshooting 25 6 Heartbeat Patterns 26 7 Hardware Default initialization 27 7 1 How to reset the FAAC Telephone Access System for Factory Default 27 8 Maintenance Recommendations 28 Appendix A Installation Checklist 29 WARRANTY 30 iii...

Страница 4: ...iv ...

Страница 5: ...ovide protection against a short circuit on the input bridge rectifier C2 etc The system requires the integrity of the subscribed telephone line to be operational at all times If the telephone line is cut off placed out of service or shared with other interconnect telephone devices other than the TAS250 the unit will not be able to perform its function when required 2 AVOID setting up the equipmen...

Страница 6: ...Technical Support For technical assistance with the FAAC Telephone Access System and other FAAC products contact technical support Monday to Friday from 8AM to 5PM Eastern 2 ...

Страница 7: ...this equipment users should ensure that it is permissible to be connected to the facilities of the local telecommunications company The equipment must also be installed using an acceptable means of connection The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations Repairs to certified equipment should be made by an authorized...

Страница 8: ... FAAC part number TR1640P CSA manufacturer part number Codex model SEP G 1640 For UL 294 Only models TAS250 125US for installation in the USA and TAS250 125CDN for installation in Canada are UL listed If the TAS250 door lock output is used in fail secure mode a listed panic hardware device shall be used to allow emergency exit from the protected area Electrical specifications refer to Table 1 on p...

Страница 9: ...ision automatic door unlock automatic relay activation pager and dialup reporting The TAS250 is designed to be a stand alone unit as well as a part of a complete access control system such as EntraPass from FAAC The TAS250 can be connected to a PC via IP or RS 485 or internal PSTN to the phone line It can communicate with EntraPass through a Corporate gateway for programming and monitoring This ma...

Страница 10: ...also programmable By default Input 1 is assigned to the door contact and Input 2 is assigned to the postal lock Each input can be individually configured for one of the following applications Door Contact Postal Lock Rex Request to Exit Device General Supervised Input DC Powered Lock Output There is one 1 onboard DC powered lock output and it is supervised Relay Outputs There are three 3 onboard r...

Страница 11: ...ivated RELAY1 RELAY2 and RELAY3 RED Each relay output has an indicator which turns ON each time the corresponding relay is activated AC POWER and DC POWER GREEN These LEDs are on when AC and DC power are present TXRX YELLOW This LED is OFF when there is no Ethernet network or the cable is disconnected FLASHING when there is an Ethernet cable and network activity and ON when the network is present ...

Страница 12: ...ed just for that purpose This illuminated enclosure supports the letter format 216 x 279 mm 8 5 x 11 in and A4 format 210 x 297 mm 8 3 x 11 7 in Figure 3 Paper Index Flush Mounted Camera The TAS250 offers the possibility to install a color camera in the back of the front door Figure 4 Camera Position in Back of Front Door 8 ...

Страница 13: ...is option fits in the product enclosure Its role is to allow postal service personnel access to the building For added security purpose its usage may be limited by a schedule Figure 5 Postal Lock Mounting Location 9 ...

Страница 14: ...Goose Neck The TAS250 can be mounted on a goose neck stand Figure 6 Goose Neck Mounting Plate with Gaskets Goose Neck not Included 10 ...

Страница 15: ...work Remotely with EntraPass over RS 485 Remotely with EntraPass over the telephone line with a dialup modem Figure 7 TAS250 Configurations with EntraPass Note For the UL 294 Compliance the TAS250 125US and TAS250 125CDN models must be integrated with an access control system over a Wiegand connection 11 TAS250 Integrated with FAAC Access Control System TAS250 TAS250 TAS250 ...

Страница 16: ...Figure 8 PCB view of main board 12 ...

Страница 17: ...Figure 9 TAS250 Wiring Example with an External Controller UL Compliant North America 13 ...

Страница 18: ...Figure 10 TAS250 Wiring Example with Reader Stand Alone Application North America 14 ...

Страница 19: ...F Telephone Line 305 m 1 000 ft maximum RS 485 Bus 1219 m 4 000 ft maximum Ethernet network 91 m 300 ft maximum 29 21 cm 11 1 2 in Wide x 37 46 cm 14 3 4 in High x 9 91 cm 3 9 in Deep 10 100 Base T Ethernet Port RJ 45 connector 1 x RS 485 COM1 Global Data Access Arrangement DAA interface for the telephone line Ethernet 10 100 Base T RS 485 from 1200 to 115 200 Baud automatic detection Dialup Modem...

Страница 20: ...scription Paper Index Surface Mount Paper Index Black Trim Ring Goose Neck Mounting Plate 29 21 cm 11 1 2 in Wide 37 46 cm 14 3 4 in High 9 93 cm 4 in Deep 35 72 cm 14 in Wide 44 13 cm 17 3 8 in High 0 92 cm 3 8 in Deep 25 30 cm 10 in Wide 36 50 cm 14 3 8 in High 3 30cm 1 1 4 in Deep 1 for Auxiliary Power 11 2 to 13 75 VDC 2 for Controlled Readers 11 2 to 13 75 VDC 2 for Controlled Readers 5 VDC 1...

Страница 21: ... or wiring and from electrical equipment susceptible of generating electrical interference and at a minimum of 8 m 25 ft from any transmitting equipment 4 2 Installation STEP 1 Unpacking the TAS250 Check that the following parts are in your TAS250 package when you unpack it FAAC Telephone Access System TAS250 EntraPass software CD ROM version 4 02 or higher Installation Manual English and French v...

Страница 22: ...ot higher than 117 cm 46 in from the floor If you install it in a location where there are extremely low temperatures the outdoor installation might require an optional heater kit in order to meet the environmental conditions Caution Make sure the area stays clear of any objects below the TAS250 that could interfere with its daily use 18 ...

Страница 23: ...uch as an electromechanical strike and can be configured to operate fail safe or fail secure normal or reverse action Note Use 1 K ohm EOL End of Line resistor between LK and LK terminals if not used STEP 5 Connecting the Door Lock Device with an External Power Supply Use one of the three relay terminals available to connect the door locking device and the external power supply STEP 6 Hooking Up I...

Страница 24: ... NO device the alarm state will be given when the input is shorted EOL with EOL resistor The secure state is given when a single resistor is detected The alarm state is given when the input is open or short DEOL Double EOL Resistor For NC device only in a DEOL configuration the secure state is given when a single resistor is detected The alarm state is given when two resistors in series are detect...

Страница 25: ... is set by jumper JP9 5V 12V or EXT STEP 9 Connecting the Telephone Line Connect the TIP green and RING red from the Phone Line to the TIP and RING terminals Note The T 1 and R 1 terminals can be connected to the local telephone STEP 10 Connecting the RS 485 optional 21 ...

Страница 26: ...n and the telephone line proper grounding is required to insure safety and proper operation An AWG 18 single conductor copper wire must be used to ground each TAS250 to good earth ground as per the local electrical code be careful with ground loops The ground clamp should be located below any other ground STEP 13 Connect AC Power Power should only be applied to the unit when all connections are co...

Страница 27: ... 7 A h backup battery provides operation of up to 12 hours Note The battery must be kept indoor if the outdoor temperature drops below 25 C 13 F STEP 15 Connecting the Heater Kit for Outdoor Operation Optional Refer to the Heater Kit Install Sheet 23 ...

Страница 28: ...tend to program the TAS250 remotely with an access control software like EntraPass there are some options that must be done with the VUI before leaving the customer premises Enter the TAS250 programming mode by pressing and holding during 5 seconds until you hear a beep Type in the Installer PIN 8888 Important For security reasons keep in mind to change the default installer PIN 8888 after the ins...

Страница 29: ...Reset Internal RTC Real Time Clock and clock are settled to the default time and date values January 1st 2009 00 00 00 Factory Default When JP1 and JP2 are OFF The default installer PIN 8888 is restored All TAS250 memory is settled to default values Internal event buffer is cleared TAS250 generates the message TAS250 Factory Default Reset Internal RTC and clock are settled to the default time and ...

Страница 30: ... to Table 4 if you must reset or change the communication mode with the TAS250 Table 6 Heartbeat Patterns Booting Up Steady Factory Default Continuous LONG pulses Forced Default Static 3 Long Pulses Modem Initialization Single 2 5 Sec Burst Dialup Communication with EntraPass Corporate Gateway Communication with EntraPass Hard Reset 2 Short Pulses 3 Short Pulses 4 Short Pulses Fail Soft Continuous...

Страница 31: ...AS250 with the key Locate the reset button SW1 and the two jumpers JP1 JP2 See the flashing blue Heartbeat LED 1 Remove JP1 and JP2 jumpers as described in Table 4 for Factory Default 2 Press the reset button 3 Check the blue Heartbeat LED pattern wait until the heartbeat pattern corresponds to this Continuous LONG pulses 4 Put back JP1 and JP2 jumpers close and lock the TAS250 5 Configure the TAS...

Страница 32: ...ly dry chemical fire extinguishers Do not use water to put out the fire Do not heat the batteries Do not dispose of the batteries or circuit board in a fire Do not disassemble the batteries Do not apply pressure to or deform the batteries Ensure that the above precautions are strictly observed by related departments including but not limited to production sales and outside contractors It is highly...

Страница 33: ...250 on the Same Telephone Line optional STEP 13 Connect the TAS250 to Earth Ground STEP 14 Connect AC Power North America only STEP 15 Connect DC Power EMEA only STEP 16 Connecting the Backup Battery STEP 17 Connecting the Heater Kit for Outdoor Operation Optional STEP 18 Connecting the Ethernet Cable Optional STEP 19 Powering Up the TAS250 STEP 20 Programming the TAS250 Appendix A Installation Ch...

Страница 34: ...f the product s or has been subject to misuse negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceeding those set forth in the specifications for such product s Neither FAAC S p A nor FAAC International Inc shall be liable for any loss or damage whatsoever re...

Отзывы: