FSW OP - Opening safety devices contact (terminal 3):

 The

purpose of the opening safety devices is to protect the leaf
movement area during opening.

 

During opening, in the 

A-

AP-S-E-EP

 logics the safety devices reverse the movement

of the gate leaves, or stop and restart the movement when
they are released (see advanced  programming in Chpt
5.2). During the opening cycle in logics 

B

 and 

C

, they

interrupt movement. They never operate during the closing
cycle.
If the 

Opening safety devices

 are engaged when the gate

is closed, they prevent the leaf opening movement.
To install several safety devices, connect the N.C. contacts
in series (fig.4).

NB.: If no opening safety devices are connected, jumper
connect inputs OP and -TX FSW 

(fig. 5).

FSW CL - Closing safety devices contact (terminal 4):

 The

purpose of the closing safety devices is to protect the leaf
movement area during closing. During closing, in the 

A-

AP-S-E-EP 

logics, the safety devices reverse the movement

of the gate leaves, or stop and reverse the movement
when they are released (see advanced  programming in
Chpt 5.2). During the closing cycle in logics 

B

 and 

C

, they

interrupt movement. They never operate during the
opening cycle. If the 

Closing safety devices

 are engaged

when the gate is open, they prevent the leaf closing
movement.
To install several safety devices, connect the N.C. contacts
in series (fig.4).

NB.: If no closing safety devices are connected, jumper
connect terminals CL and -TX FSW

 (fig. 5).

STOP

 

- STOP contact (terminal 5):

 any device (e.g. a push-

button) which, by opening a contact, is able to stop
gate movement.
To install several STOP devices, connect the N.C. contacts
in series.

NB.:

 If STOP devices are not connected, jumper connect

the 

STOP

 and 

terminals.

EDGE - EDGE safety device contact (terminal 6):

 The purpose of

the "edge" safety device is to protect the leaf movement
area during opening/closing against fixed obstacles (pillars,
walls, etc.).  In all logics, during opening and closing, the
safety devices reverse gate leaf movement for 2 seconds.
If the safety devices operate again during the 2-seconds
reversing time, they STOP movement without any reversing.
If the 

Edge safety devices

 are engaged while the gate is

closed or open, they prevent the leaves movement.
To install several safety devices, connect the N.C. contacts
in series (fig.4).

NB.: If edge safety devices are not connected, jumper
connect the EDGE and - inputs.

 (fig. 5).

Negative for power supply to accessories (terminals 7 and
8)

+

24 Vdc - Positive for power supply to accessories (terminals
9 and 10)
Important: 

Accessories max. load is 500 mA. To calculate

absorption values, refer to the instructions for individual
accessories.

TX -FSW - Negative for power supply to photocell transmitters

(terminal 11)

If you use this terminal for connecting the negative for
supplying power to the photocell transmitters, you may,
if necessary, also use the FAIL SAFE function (see advanced
programming in Chpt 5.2).
If this function is enabled, the equipment checks
operation of the photocells before every opening or
closing cycle.

W.L. - Power supply to indicator-light / timed output (terminal

12)

Connect a 24 Vdc - 3 W max indicator-light or timed
output, if necessary, between this terminal and the +24V
supply (see advanced programming in Chpt 5.2).To
avoid geopardising correct operation of the system, 

do

not exceed

 the indicated power.

Fig. 16

Fig. 15

Fig. 17

MINIDEC

PLUS

PLUS

DECODER

RP

4.5. Connector J2 - Rapid connection to Minidec, Decoder and RP

This is used for rapid connection of Minidec, Decoder and RP
receivers (see fig. 15, 16 and 17). Connect the accessory, with the
components side facing the inside of the board. Insert and remove
after cutting power.

4.6. Connector J6 - Limit-switches rapid connection (fig.2)

This input is intended for rapid connection of the opening  and
closing  limit-switches designed to stop the leaf, or for start of
decelerations or for braking  (see advanced programming in
Chpt. 5.2.). In gearmotors with a built-in control unit, this connection
is pre-wired as standard (fig. 2). For leaf opening direction, see
advanced programming in Chpt 5.2.

4.7. Connector J3 - Encoder rapid connection (fig.2)

This input is designed for rapid connection of the Encoder
(optional). To fit the encoder on the motor, refer to the relevant
instructions.
The presence of the encoder is signalled - when the gearmotor
is running - by the flashing of the "Encoder" LED on the board.
When the encoder is used, the control unit knows the exact
position of the gate while it is moving.
The encoder controls the adjustments of some of the control
unit's functions in a different way (partial opening or deceleration
- see advanced programming in Chpt 5.2) and as an anti-
crushing device.
If the gate strikes an obstacle during opening or closing, the
encoder immediately reverses the gate leaf for 2 seconds.  If the
encoder operates again during the 2-seconds reversing time,
it STOPS movement without commanding any reversing.

748D

748D

748D

Содержание 748

Страница 1: ...N D A C E R TIF I C A T A UNI EN ISO 9001 085 para la naturaleza 100 papel reciclado ist umweltfreundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 carta riciclata 1...

Страница 2: ...ss Via Benini 1 40069 Zola Predosa BOLOGNA ITALY Declares that Operator mod 748 with electronic control unit 748D is manufactured to be incorporated in a machine or for assembly with other machines to...

Страница 3: ...eningtime Tc closingtime Tp pausetime Ti durationofintervalbetweena completecycleandthenextone 2 STANDARD INSTALLATION LAYOUT 10 20 30 40 50 60 70 80 90 100 0 1 2 3 4 5 6 7 8 9 10 10 11 12 Percentuale...

Страница 4: ...wsTE8x50are provided N B itisadvisabletotightentherackfixingscrewsatthetopoftheslot Thisallows theracktoberaisedif withtime thegatetendstosink 2 Releasetheoperator seeparagraph3 5 3 Slidethegateleafop...

Страница 5: ...s and that the electro mechanical travel limit wheel is at least 2 cm from the end of the plate s straight area if necessary adjust the slowing down time and or straighten the final profiled part of t...

Страница 6: ...transmit movement to the leaf by means of a pinion with rack coupled in appropriate manner to the sliding gate The operation of the sliding gate is controlled by an electronic control unit housed insi...

Страница 7: ...grammable from 0 to 4 min Pause time Programmable from 0 to 4 min Thrust force Adjustable over 50 levels Terminal board inputs Open Partial opening Safety devices at opng Safety devices at clsng Stop...

Страница 8: ...erefore it is suitable for protecting the opening and closing area against the risk of impact crushing shearing and dragging N B If two or more safety devices have the same function opening closing op...

Страница 9: ...ral L Power supply Line NB For correct operation the board must be connected to the earth conductor in the system Install an adequate differential thermal breaker upstream of the system 4 3 J6 Termina...

Страница 10: ...devices are not connected jumper connect the EDGE and inputs fig 5 Negative for power supply to accessories terminals 7 and 8 24 Vdc Positive for power supply to accessories terminals 9 and 10 Import...

Страница 11: ...s the opening or closing limit switch a braking stroke can be selected to ensure the leaf is stopped immediately If decelerations are selected braking starts when they finish At value braking is disab...

Страница 12: ...proceed This function can be used to check use of the board or to exploit the Assistance request Display Function Default GATE STATUS Exit from programming and return to gate status viewing see Chpt 5...

Страница 13: ...SAFETY DEVICE No effect OPEN disabled Reverses on opening for 2 2 Reverses on closing for 2 2 Table 3 b LOGIC AP PULSES GATE STATUS OPEN A OP CLOS SAFETY DEVICE CLOSING SAFETY DEVICES OPENING SAFETY D...

Страница 14: ...ops operati o n OPEN A disabled No effect OPEN B disabled Cl o ses the l e af Stops operati o n Stops operation No effect OPEN A disabled No effect CONTROLS ALWAYS HELD DOWN No effect OPEN B disabled...

Страница 15: ...a poner al d a la presente publicaci n todas las modificaciones que considere oportunas para el perfeccionamiento t cnico o para cualquier otro tipo de exigencia de car cter constructivo o comercial F...

Отзывы: