Connection of a closing safety device and an opening   

safety device

Connection of no safety device

Connection of an "edge" safety device

Connection of a pair of opening photocells

Connection of a pair of closing photocells

Before connecting the safety devices and photocells we advise  

you to select the type of operation according to the movement 

area they have to protect (see fig.3 for example):

Opening safety devices:

 they are tripped when an obstacle is 

detected only during gate opening movement. They 

cause immediate closure and resumption of opening 

motion on release (see programming in par.5.2).

Closing safety devices:

 they are tripped when an obstacle is 

detected only during gate closing movement. They 

cause re-opening, either immediate or on release (see 

programming in par.5.2).

Opening/closing safety devices:

 

they are tripped during the 

gate  opening  and  closing  movements.  They  cause 

stopping and restart motion on release.

"Edge" safety devices:

 they are tripped during the gate opening  

and  closing  movements.  They  cause  immediate  

reversal of motion and stopping after two seconds.

Encoder: 

it is tripped if there is an obstacle during gate opening 

and closing movements. It causes immediate reversal 

of motion and stopping after two seconds.

 

Note:  in  operators  for  industrial  sectional  doors,  the 

anti-crushing  function  is  not  tripped  during  closing, 

because the operator acts on the rope shaft and not 

directly on the door. 

N.B.  If  two  or  more  safety  devices  have  the  same  function 
(opening, closing, opening and closing, edge), the contacts 
must be connected to each other in series (fig. 4).
N.C. contacts must be used.
N.B:  If  safety  devices  are  not  used,  jumper  connect  the  
terminals as shown in fig. 5.

The most common photocell and safety device lay-outs are 

shown below (from fig. 6 to fig. 13). 
 

NOTE: The 578D equipment is able to command electro-mechanical  

operators for sliding gates and industrial sectional doors. Anything 
referring to gates in these instructions also applies to doors. Any 
differences are shown in the specific paragraphs.

Closing  

photocells

Opening or  

opening/closing  

photocells

"Edge" safety devices

4.1 Connection of photocells and safety devices

Closing photocells

Connection of two N.C. contacts in series

(e.g.  Photocells, Stop, Edge, etc.)

Содержание 578D

Страница 1: ...4 4 J1 TERMINAL BOARD ACCESSORIES FIG 2 6 4 5 CONNECTOR J2 RAPID CONNECTION TO MINIDEC DECODER AND RP 7 4 6 CONNECTION OF OPERATOR 844 7 4 7 CONNECTION OF OPERATOR 541 7 4 8 CONNECTION OF OPERATORS W...

Страница 2: ...an adequate level of safety the Standards mentioned above must be observed in addition to national legal regulations 11 Before attempting any job on the system cut out electrical power 12 The mains po...

Страница 3: ...ON Power supply V 6 10 230 Absorbed power W 10 Motor max load W 1000 Accessories max load A 0 5 Operating ambient temperature 20 C 55 C Protection fuses 2 see fig 1 Function logics Automatic Stepped a...

Страница 4: ...sing movements They cause immediate reversal of motion and stopping after two seconds Encoder itistrippedifthereisanobstacleduringgateopening and closing movements It causes immediate reversal of moti...

Страница 5: ...photocells and a pair of opening closing photocells Connection of a pair of closing photocells a pair of opening photocells and a pair of opening closing photocells Connection of a pair of opening pho...

Страница 6: ...contact stops gate movement To install several STOP devices connect the N C contacts in series fig 4 NB IfSTOPdevicesarenotconnected jumperconnect the STOP and terminals SAFE EDGEsafetydevicecontact...

Страница 7: ...h respectto theconnectionbetweentheSTOPinputof578D and the SAFETY of the 541 INTERFACE Refer to paragraph 6 3 for instructions on putting into operation To make connections between the 578D equipment...

Страница 8: ...FC1 FC2 2 1 FC1 FC2 ENGLISH Fig 21 Fig 19 Fig 20...

Страница 9: ...Disabled FINAL BRAKING When the gate engages the opening or closing limit switch a braking stroke can be selected to ensure the leaf is stopped immediately If decelerations are selected braking starts...

Страница 10: ...or they reverse it immediately Y Reverse immediately to closing no Restart movement on release ENCODER Iftheencoderisused youmayselectitspresence If the encoder is present and enabled decelerations a...

Страница 11: ...nd activated Command inactive OP B Command activated Command inactive FC1 Limit switch free Limit switch engaged FC2 Limit switch free Limit switch engaged FW OP Safety devices disengaged Safety devic...

Страница 12: ...crushing system ANTI CRUSHING SAFETY DEVICE DURING CLOSING although it has an Encoder sensor the 541 operator cannot intrinsically guarantee this safety device because it is not fitted directly on th...

Страница 13: ...f with Closing Safety devices engaged opens at the 2nd pulse 3 No effect OPEN disabled No effect No effect OPEN disabled Tab 3 b Logic S PULSES GATE STATUS OPEN A OPEN B STOP OPENING SAFETY DEVICES CL...

Страница 14: ...ETY DEVICES OP CL SAFETY DEVICE EDGE SAFETY DEVICE CLOSED Opens the leaf No effect No effect OPEN A disabled No effect No effect OPEN A disabled OPEN No effect Closes the leaf No effect OPEN B disable...