1. PROGRAMMING THE MICROSWITCHES

Automation programming is carried out by the microswitches
(fig. 1 - ref. 9) as shown in the diagram below.

If the gate closes, invert the motor wires on the control unit
(brown and black wires).

2.2. OPERATION TIME ADJUSTMENT

Opening/closing times are set by the OP/CL trimmer on the
control unit (fig. 1 - ref.7).
To reduce operation time, adjust the trimmer anticlockwise
To increase operation time, adjust the trimmer clockwise.
Maximum operation time is 120 seconds.
For 90° opening the approximate opening/closing time is 18
seconds.
For optimal system efficiency set the opening/closing time so
that the electric motor remains activated for a few seconds
after the leaf has reached the mechanical travel stop.

2.3. CLOSING LEAF DELAY ADJUSTMENT

In the case of overlapping leaves, it is possible to delay closing
of the leaf driven by motor M1 (see fig. 2) to ensure correct
closure of the gate.
Set the delay by the LEAF DELAY trimmer on the 410 MPS control
unit (fig. 1 - ref. 8).
To reduce delay time, adjust the trimmer anticlockwise.
To increase delay time, adjust the trimmer clockwise.
Maximum delay time is 28 seconds. If the operation time is
shorter, the delay time is reduced automatically.

2.4. SETTING PAUSE TIME

When A, S or AD logics are selected, the leaf momentary stop
time can be set using the PAUSE trimmer (fig. 1 ref. 6).
Turn the trimmer clockwise to increase the time.
Turn the trimmer anticlockwise to reduce the time.
The maximum pause time is 240 sec.

2.5. ANTI-CRUSHING SYSTEM ADJUSTMENT

The 410 MPS control unit has been designed for use on both
electromechanical and hydraulic operators.
When the 410 MPS card is used on electromechanical operators,
the torque control device must be set by turning the TORQUE
trimmer (fig. 1 ref. 5).
To reduce torque, adjust the trimmer anticlockwise.
To increase torque, adjust the trimmer clockwise.
In any event, FAAC advises not to exceed a torque of 15 Kg
measured on the outer edge of the leaf.
To ensure precise torque adjustment use a linear dynamometer.
When the 410 MPS card is used on hydraulic operators, the
torque control device must be set to the maximum value by
turning the TORQUE trimmer clockwise.
This device is already present inside the operator hydraulic
circuit (BY-PASS valves).

1.1. OPERATION LOGICS

There are four operating logics available:

A : “AUTOMATIC ”

E : “SEMI-AUTOMATIC”

S : “SAFETY”

EP : “SEMI-AUTOMATIC STEP-BY-STEP”
AD: "AUTOMATIC TIMER"

Operation of the different logics is described in tables 3/a-b-c-d-
e.

1.2. SAFETIES ON CLOSING

This function serves to select the operating mode for the closing
safeties:

- OFF: immediate reverse of movement during gate closure
- ON: movement is stopped during closing and reversed on

opening when the safety is disengaged.

2. START-UP

1)

Program the 410 MPS electronic control unit according to
specific requirements as shown in fig. 15.

2)

Check led status as shown in table.

LED functions

LEDS

ON

OFF

DL 1 (OPEN INPUT A)

Command active

Command not active

DL 3 (STOP)

Command not active

Command active

DL 4 (FTSW OPEN)

Safeties disengaged

Safeties engaged

DL 5 (FTSW CLOSE)

Safeties disengaged

Safeties engaged

N.B.:

 the bold text indicates led status with gate idle.

2.1. DIRECTION OF ROTATION

1)

Switch off the power.

2)

Manually move the gate to halfway.

3)

Lock the operators.

4)

Switch on the power.

5)

Send an OPEN signal to input A (fig. 2) and check that the
leaf opens.

Fig. 15

OPERATING

LOGICS

SAFETIES ON CLOSING

INVERTS MOVEMENT
IMMEDIATELY

STOPS AND INVERTS
MOVEMENT ON
DISENGAGEMENT

AD

A

S

E

EP

OFF

ON

OFF

OFF

ON

OFF

OFF

OFF

OFF

ON

ON

OFF

SW1

SW2

SW3

SW4

OFF

ON

ON

ON

OFF

1

2

3

4

Fig. 14

Enable

Disable

Disable

Enable

FAIL-SAFE

LEAF DELAY

Intelligent Security & Fire Ltd.

Содержание 410 MPS

Страница 1: ... pour la nature papier recyclé 100 for nature recycled paper 100 per la natura carta riciclata 100 para la naturaleza 100 papel reciclado C ERME T A Z I E N D A C E R TIF I C A T A UNI EN ISO 9001 085 I n t e l l i g e n t S e c u r i t y F i r e L t d ...

Страница 2: ... installation with an opening distance of the contacts of 3 mm or more Alternatively use a 6A thermomagnetic breaker with multi pole switching 13 Ensure that there is a differential switch up line of the electrical system with a trip threshold of 0 03A 14 Check that the earthing plant is in perfect condition and connect it to the metallic parts Also earth the yellow green wire of the operator 15 T...

Страница 3: ...es section N B The capacitors are provided with the operators Fig 2 Warning the max accessory load is 250 mA To calculate absorption values refer to table 2 Safety devices These are all devices photocells safety edges magnetic coils etc with an N C normally closed contact which activate if an obstacle obstructs the area protected by the a J1 terminal block fig 2 Earth connection N power supply 230...

Страница 4: ...tch SW4 settings They do not engage during the opening cycle N B If closing safety devices are not connected jumper inputs OP and FSWTX fig 4 The purpose of the closing safety devices is to safeguard the zone in which the leaves move during the closing cycle B fig 3 If the Fail Safe function is not used see cabling at page 4 for connections of photocells Important for further information on the op...

Страница 5: ... 30Vcc OP CL FSW FSWTX Two pair of closure photocells connected Fig 4 A Fig 5 A Fig 6 A Fig 7 A Fig 8 A Fig 9 A Application examples The following are the commonly used connection arrangements disable fail safe No safety device connected One pneumatic edge connected as closing safety device and one connected as opening safety device 1 pair of closing photocells connected 1 pair of opening photocel...

Страница 6: ...adjusting trimmer Time is adjustable from 0 to 120 seconds h LEAF DELAY trimmer closing leaf delay adjusting trimmer Leaf delay time is adjustable from 0 to 28 seconds N B 1 If the opening closing time is less than the set delay time the delayed leaf closes at the end of the closing time 2 In one leaf application set the leaf delay time to minimum i Programmingmicroswitches j Fuse F1 5x20 5 A 250 ...

Страница 7: ... the TORQUE trimmer fig 1 ref 5 To reduce torque adjust the trimmer anticlockwise To increase torque adjust the trimmer clockwise In any event FAAC advises not to exceed a torque of 15 Kg measured on the outer edge of the leaf Toensureprecisetorqueadjustmentusealineardynamometer When the 410 MPS card is used on hydraulic operators the torque control device must be set to the maximum value by turni...

Страница 8: ...ffect OPEN inhibited OPENING No effect OPEN inhibited Stops closing and when disengaged opens See paragraph 1 2 Stops opening and when disengaged continues to open No effect Stops No effect OPEN inhibited Closes leaf leaves No effect OPEN inhibited No effect No effect OPEN inhibited No effect STOPPED CLOSING OPEN Recloses leaves immediately Reopens leaves immediately PULSES OPENING CLOSING SAFETIE...

Страница 9: ...ps opening and when disengaged closes LOGICS AD PULSES GATE STATUS OPEN A OPENING CLOSING SAFETIES CLOSING SAFETIES OPENING SAFETIES STOP Table 3 e CLOSED OPEN on PAUSE CLOSING OPENING If held it remains in pause timer function No effect OPEN inhibited Stops closing and when disengaged opens See paragraph 1 2 Stops opening and when disengaged continues to open No effect No effect No effect OPEN in...

Страница 10: ...licación todas las modificaciones que considere oportunas para el perfeccionamiento técnico o para cualquier otro tipo de exigencia de carácter constructivo o comercial FAAC S p A Via Benini 1 40069 Zola Predosa BO ITALIA Tel 051 6172411 Tlx 521087 Fax 051 758518 FAAC per la natura La presente istruzione è realizzata al 100 in carta riciclata Non disperdete nell ambiente gli imballaggi dei compone...

Отзывы: