SLAVE BOARD CONNECTION TERMINAL BOARD
Terminals 1-2-3= passing connection to 28-27-26 with protective fuse
Terminals 4-5-6-7-8 = connection for hydraulic power pack
Terminals 9-10 = connection for automatic lowering in the event of a 230V power cut
Terminals 11-12 = connection to safety pressure switch
Terminal 13 = common contact for limit-switch - buzzer - FAAC CITY flashing light
Terminal 14 = connection to FAAC CITY low limit-switch
Terminal 15 = connection for FAAC CITY intermittent buzzer
Terminal 16 = connection for flashing light incorporated into the head of FAAC CITY
Terminal 17 = common contact for limit-switch - buzzer - FAAC CITY flashing light
Terminals 18-19-20 = connection to service transformer
Terminal 21 = not used
Terminals 22-23= 230V connection to electronic circuit
Terminal 24 = not used
Terminal 25 = earth connection
Terminals 26-27-28= passing connection to 3-2-1 with (protective fuse)